Ntp- D343 Sncp Acceptance Test - Cisco ONS 15454 SDH Procedure Manual

Hide thumbs Also See for ONS 15454 SDH:
Table of Contents

Advertisement

Chapter 5
Turn Up a Network
VC3—If you are testing a clear channel E3/DS3I, you must have a patch panel or a direct E3/DS3I
interface into the ONS 15454 SDH. Set the test set for clear channel E3/DS3I. For information about
configuring your test set, consult your test set user guide.
VC12—If you are testing an E1, you must have a patch panel or a direct E1 interface to the
ONS 15454 SDH. Set the test set for E1. For information about configuring your test set, consult
your test set user guide.
VC11—If you are testing a VC11 circuit on an STM-N or MRC-12 card, you must have a direct
optical interface to the ONS 15454 SDH. Set the test set for STM-N. For information about
configuring your test set, consult your test set user guide.
Verify the integrity of all patch cables that will be used in this test by connecting one end to the test set
Step 8
transmit (Tx) connector and the other end to the test set receive (Rx) connector. If the test set does not
run error-free, check the cable for damage and check the test set to make sure it is set up correctly before
continuing.
Create a physical loopback at the circuit destination card:
Step 9
a.
Attach one end of a patch cable to the destination port's transmit (Tx) connector.
b.
Attach the other end to the port's receive (Rx) connector.
Step 10
At the circuit source card:
a.
Connect the transmit (Tx) connector of the test set to the circuit receive (Rx) connector.
Connect the test set receive (Rx) connector to the circuit transmit (Tx) connector.
b.
Verify that the test set shows a clean signal. If a clean signal does not appear, repeat Steps
Step 11
to make sure the test set and cabling are configured correctly.
Inject BIT errors from the test set. To verify that you have a complete end-to-end circuit, verify that the
Step 12
errors appear at the test set.
Step 13
Complete the
Step 14
Complete the
From the View menu, choose Go to Network View.
Step 15
Click one of the two spans leaving the circuit source node.
Step 16
Compete the
Step 17
protection switching function on this span.
In network view, click the other circuit source span and repeat Step 17.
Step 18
Set up and complete a BER Test. Use the existing configuration and follow your site requirements for
Step 19
the length of time. Record the test results and configuration.
Complete the
Step 20
Remove any loopbacks, switches, or test sets from the nodes after all testing is complete.
Step 21
Click the Alarms tab.
Step 22
Verify that the alarm filter is not on. See the
a.
page 19-25
Verify that no unexplained alarms appear on the network. If unexplained alarms appear, resolve
b.
them before continuing. Refer to the Cisco ONS 15454 SDH Troubleshooting Guide if necessary.
Complete the
c.
78-17194-01
"DLP-D254 TCC2/TCC2P Card Active/Standby Switch Test" task on page
"DLP-D255 Cross-Connect Card Side Switch Test" task on page
"DLP-D94 SNCP Protection Switching Test" task on page 17-91
"DLP-D27 Delete Circuits" task on page 17-21
as necessary.
"DLP-D147 Export CTC Data" task on page 18-38

NTP- D343 SNCP Acceptance Test

for the test circuit.
"DLP-D227 Disable Alarm Filtering" task on
to export alarm information.
Cisco ONS 15454 SDH Procedure Guide, R7.0
1
through
6
19-59.
19-60.
to test the SNCP
5-25