NTP- D6 Install the Power and Ground

NTP-D6 Install the Power and Ground
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Warning
Statement 1003
Warning
This equipment is intended to be grounded. Ensure that the host is connected to earth ground during
normal use. Statement 39
Warning
Use copper conductors only. Statement 1025
Warning
Connect the unit only to DC power source that complies with the safety extra-low voltage (SELV)
requirements in IEC 60950 based safety standards. Statement 1033
This product requires short-circuit (overcurrent) protection, to be provided as part of the building
Warning
installation. Install only in accordance with national and local wiring regulations. Statement 1045
Cisco ONS 15454 SDH Procedure Guide, R7.0
1-10
This procedure installs power feeds and grounds the ONS 15454 SDH.
#2 Phillips screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Screws
Power cable (from fuse panel to MIC-A/P and to MIC-C/T/P), shipped with
the ONS 15454 SDH
Ground cable 13.3-mm² (#6 AWG) stranded
Two-hole grounding lug, shipped with the ONS 15454 SDH
Listed pressure terminal connectors such as ring and fork types; connectors
must be suitable for 8.36-mm² (#8 AWG) copper conductors
Wire cutters
Wire strippers
Crimp tool
Fuse panel
NTP-D219 Open and Remove the FMEC Cover, page 1-7
NTP-D220 Install the Power and Signal FMECs, page 1-7
and MIC-C/T/P)
Required
Onsite
None
Chapter 1
Install the Shelf and FMECs
(for MIC-A/P
78-17194-01