DLP- D332 Install the TCC2/TCC2P Cards
Verify that the ACT/STBY LED is green for active if this is the first powered-up TCC2/TCC2P card
Step 5
installed, or yellow for standby if this is the second powered-up TCC2/TCC2P. The IP address,
temperature of the node, and time of day appear on the LCD. The default time and date is 12:00 AM,
January 1, 1970.
The LCD cycles through the IP address (the default is 192.1.0.2), node name, and software version.
Step 6
Verify that the correct software version displays on the LCD. The software text string indicates the node
type (SDH or SONET) and software release.( For example: SDH 07.00-05L-20.10 indicates it is an SDH
software load, Release 7.00. The numbers following the release number do not have any significance.)
If the LCD shows the correct software version, continue with
Step 7
correct software version, upgrade the software or remove the TCC2/TCC2P card and install a
replacement card.
Refer to the release-specific software upgrade document to replace the software. To exchange the
TCC2/TCC2P card, see the Cisco ONS 15454 SDH Troubleshooting Guide.
Repeat Steps
Step 8
Tip
Note
Note
Verify that the ACT/STBY LED is amber for standby.
Step 9
Return to your originating procedure (NTP).
Step 10
Cisco ONS 15454 SDH Procedure Guide, R7.0
20-24
1
through
7
for the redundant TCC2/TCC2P card.
If you install a standby TCC2/TCC2P card that has a different software version than the active
TCC card, the newly installed standby TCC2/TCC2P card automatically copies the software
version from the active TCC2/TCC2P card. You do not need to do anything in this situation, but
the loading TCC2/TCC2P card does not boot up in the normal manner. When the standby card
is first inserted, the LEDs follow most of the sequence listed in
FAIL LED turns on for about 5 seconds, the FAIL LED and the ACT/STBY LED begin to flash
alternately for up to 30 minutes while the new software loads onto the active TCC2/TCC2P card.
After loading the new software, the upgraded TCC2/TCC2P card's LEDs repeat the sequence
from
Step
4, and the amber ACT/STBY LED turns on.
If you insert a card into a slot provisioned for a different card, all LEDs turn off.
Alarm LEDs might be on; disregard alarm LEDs until you are logged into CTC and can view the
Alarms tab.