Digital Outputs H2-01 to H2-03

Parameters H2-01, H2-02 and H2-03 assign functions to digital output terminals
MA, MB, MC, P1, and P2. Set these parameters as required by the application.
Default values are listed below.
No.
H2-01
Terminal MA, MB and MC Function Selection (relay) E: Fault
H2-02
Terminal P1 Function Selection (open-collector)
H2-03
Terminal P2 Function Selection (open-collector)
Note: The setting range for H2-01 through H2-03 is 0 to 4D.
page 331
for more information.
Figure 4.25
Multi-Function Contact Outputs
250 Vac, 10 mA - 1 A
30 Vdc, 10 mA - 1 A
(standard default setting)
Multi-Function Open-collector Outputs
48 Vdc, 50 mA or less
(standard default setting)

Motor Protection

This section explains how to set motor overload protection.
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Parameter Name
Figure 4.25 Digital Output Connection Diagram
4.4 Basic Parameter Adjustments
Default
0: During Run
2: Speed Agree 1
Refer to Parameter List on
Fault
MA
MA
MB
MB
MC
MC
During Run
P1
Speed Agree
P2
Open-collector Common
PC
Page
4
155