D.3

UL Standards

The UL/cUL mark applies to products in the United States and Canada indicates that UL has performed product testing and evaluation and determined
that their stringent standards for product safety have been met. For a product to receive UL certification, all components inside that product must also
receive UL certification.
u

UL Standards Compliance

This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The following conditions must be met to maintain
compliance when using this drive in combination with other equipment:
Installation Area
n
Do not install the drive to an area greater than pollution severity 2 (UL standard).
Main Circuit Terminal Wiring
n
Yaskawa recommends using UL-listed copper wires (rated at 75°C) and closed-loop connectors or CSA-certified ring connectors sized for the selected
wire gauge to maintain proper clearances when wiring the drive. Use the correct crimp tool to install connectors per manufacturer recommendation.
Table D.4
lists a suitable closed-loop connector manufactured by JST Corporation.
Wire Gauge
Terminal
2
Screws
mm
(AWG)
M3.5
0.75 (18)
M3.5
1.25 (16)
M3.5
2 (14)
3.5/5.5 (12/10)
8 (8)
14 (6)
22 (4)
30/38 (3/2)
Note: Use the specified crimp terminals (Model 14-NK4) when using CIMR-Vo2A0030, Vo2A0040, Vo4A0023 with 14 mm
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable temperature of 75°C 600 Vac UL-
approved vinyl-sheathed insulation.
Drive Model CIMR-Vo
BA0001
BA0002
BA0003
BA0006
BA0010
BA0012
BA0018
2A0001
2A0002
2A0004
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Figure D.7 UL/cUL Mark
Table D.4 Closed-Loop Crimp Terminal Size (JIS C 2805) (same for 200 V and 400 V)
Crimp Terminal
Model Numbers
R1.25-3.5
M4
R1.25-4
R1.25-3.5
M4
R1.25-4
R2-3.5
M4
R2-4
M5
R2-5
M6
R2-6
M4
R5.5-4
M5
R5.5-5
M6
R5.5-6
M8
R5.5-8
M4
R8-4
M5
R8-5
M6
R8-6
M8
R8-8
M4
R8-4
M5
R14-5
M6
R14-6
M8
R14-8
M6
R22-6
M8
R22-8
M8
R38-8
Table D.5 Recommended Input Fuse Selection
200 V Class Single-Phase Drives
200 V Class Three-Phase Drives
U L
C
US
R
LISTED
Time Delay/
Class RK5 Fuses
600 Vac, 200 kAIR
TRS5R
TRS10R
TRS20R
TRS35R
TRS50R
TRS60R
Contact Yaskawa
TRS5R
TRS5R
TRS10R

D.3 UL Standards

Tightening Torque
N m (lb to in.)
0.8 to 1.0 (7.1 to 8.9)
1.2 to 1.5 (10.6 to 13.3)
0.8 to 1.0 (7.1 to 8.9)
1.2 to 1.5 (10.6 to 13.3)
0.8 to 1.0 (7.1 to 8.9)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
4.0 to 5.0 (35.4 to 44.3)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
4.0 to 5.0 (35.4 to 44.3)
9.0 to 11.0 (79.7 to 97.4)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
4.0 to 5.0 (35.4 to 44.3)
9.0 to 11.0 (79.7 to 97.4)
1.2 to 1.5 (10.6 to 13.3)
2.0 to 2.5 (17.7 to 22.1)
4.0 to 5.0 (35.4 to 44.3)
9.0 to 11.0 (79.7 to 97.4)
4.0 to 5.0 (35.4 to 44.3)
9.0 to 11.0 (79.7 to 97.4)
9.0 to 11.0 (79.7 to 97.4)
2
(6 AWG).
Fuse Ampere Rating
5
10
20
35
50
60
5
5
10
D
353