Drive Duty and Carrier Frequency Selection: C6-01 and C6-02

n
Drive Duty Selection: C6-01
The drive has two different duty modes from which to select based on the load characteristics.
The drive rated current, overload capacity, and carrier frequency will change depending upon
the duty mode selection. Use parameter C6-01 (Duty Cycle) to select Heavy Duty (HD) or
Normal Duty (ND) for the application. The default setting is ND.
page 197
for details about the rated current.
HD and ND Mode Selections
Mode
C6-01
150 %
100 %
Characteristics
Use HD Rating is designed applications
Application
requiring a high overload tolerance with
constant load torque, like conveyors.
Overload capability
100% continuous, 150% of drive rated current
(oL2)
for 60 s
C6-02
L3-02 Stall
Prevention during
Acceleration
L3-06 Stall
Prevention during
Run
Note:
1. By selecting HD/ND, motor parameter E2 is changed to the value for the maximum applicable motor.
2. Swing PWM uses 2.0 kHz carrier frequency as a base. The application of special PWM patterns
keeps the audible noise of the motor low.
YASKAWA ELECTRIC TOEP C710606 26B YASKAWA AC Drive – J1000 Quick Start Guide
HD Rating
0
Overload
Rated Load
0
Motor Speed
2.0 to 15.0 kHz (default depends on drive capacity)
150%
150%
http://nicontrols.com
4.5 Basic Operation
Refer to Specifications on
ND Rating
120 %
100 %
0
100 %
Use ND Rating for applications in which the
torque requirements drop along with the speed.
Examples include fans or pumps where a high
overload tolerance is not required.
100% continuous, 120% of drive rated current
for 60 s
1
Overload
Rated Load
Motor Speed
100 %
120%
120%
95
4