AL-1323 (INPUT POWER OVERVOLTAGE (CONV))

Excessive input-voltage of SERVOPACK may damage the regenerative resistor.
CAUTION
Before checking the wiring connections, turn
OFF the control power supply.
Use a tester to confirm that all the LEDs on
the SERVOPACK and converter are unlit and
that no charged electricity remains.
(It may take a few minutes until all the
electricity is discharged.)
Converter
SERVOPACK
CN30
CN1
Fig. 8
Replace the converter.
Alarm?
Yes
Replace the WRCA01 circuit board.
Alarm?
Yes
Contact your Yaskawa
representative.
Is the converter's primary voltage
200 V (+10% to 15%)? (See Fig. 9.)
Yes
No
Change the breaker's primary voltage
to the specified voltage.
No
No
No
Continue normal
operation.
D o e s t h e a l a r m o c c u r
when the servo is OFF?
No
Replace the converter.
Yes
Alarm?
Yes
Continue normal
operation.
Converter
L1 L2 L3 B1 B2
Measure the voltage between L1 and L2, L1 and L3, and L2 and L3
to confirm the voltage is less than 200V + 10%.
42
An alarm
occurs.
Yes
Remove connector CN30 on the
WRCA01 circuit board and re-insert it.
(See Fig. 8.)
Alarm?
Yes
Remove connector CN1 on the
converter and re-insert it. (See Fig. 8.)
Alarm?
Yes
Alarm?
No
Replace the WRCA01 circuit board.
Alarm?
Yes
Contact your Yaskawa
representative.
Tester
(Measure the
resistance.)
Fig. 9
No
No
Continue normal
operation.
No
Continue normal
operation.