4.6 Basic Drive Setup Adjustments
• Disable motor protection (L1-01 = 1) when running multiple motors from the same drive.
Attach a thermal relay for each motor to provide overload protection.
• Use L1-13 (Continuous Electrothermal Operation Selection) to select whether the
electrothermal value is "held" or "not held" when power supply is turned off. Default
setting is 1 (Enabled).
• In the case of a general purpose (standard) motor, the cooling capability is reduced at a
low speed. Motor overload protection (OL1) may occur in frequencies lower than motor
rated current. Use an exclusive-use or inverter-duty motor to operate the drive at rated
current at low frequency.

Drive Status Monitors: U1-01 to U6-19

Parameter group U displays various data regarding the operating status of the drive.
The following example demonstrates viewing output voltage reference (U1-06).
1.
Turn on the power to the drive. The initial display appears.
Press
until "Monitor Display" appears.
2.
Press
to enter the Parameter Setting Screen.
3.
4.
Press
until U1-06 appears.
Press
to display the voltage reference. The Output Voltage
5.
Reference appears.
Refer to Parameter List on page 305
No.
Parameter Name
U1-01 Frequency Reference
U1-02 Output Frequency
U1-03 Output Current
U1-04 Control Mode
150
Step
Table 4.22 Drive Status Monitors
YASKAWA ELECTRIC TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
for more details about Drive Status Monitors.
Page
No.
372
U3-10 10th Most Recent Fault
Cumulative Operation Time at Most
372
U3-11
Recent Fault
Cumulative Operation Time at 2nd
373
U3-12
Most Recent Fault
Cumulative Operation Time at 3rd
373
U3-13
Most Recent Fault
Display/Result
Parameter Name
Page
378
378
378
378