Connect the wires to the AC terminal block on the three-phase delta wiring tray
7.
(Figure 165 on page
421). Use a 1/4-in. slotted screwdriver to loosen the input terminal
or grounding point screw, insert each wire into the grounding point or input terminal,
and tighten the screw to between 23 in-lb (2.6 Nm) and 25 in-lb (2.8 Nm).
CAUTION:
You must use an appropriate torque-controlled tool to tighten
the screws on the terminal block. Applying excessive torque damages the
terminal block and the wiring tray. The absolute maximum torque that
may be applied to this screw is 50 in-lb (5.6 Nm).
Insert the wire labeled
a.
Insert the wire labeled
b.
Insert the wire labeled
c.
Insert the wire labeled
d.

Figure 165: Connecting Power to a Three-Phase Delta AC Power Supply

L3
L2
L1
NOTE:
The color of each AC power wire might vary.
Verify that the power cable connections are correct.
8.
Chapter 29: Installing a QFX3008-I Interconnect Device
GND
into the grounding point labeled
L1
into the
L1
input terminal.
L2
into the
L2
input terminal.
L3
into the
L3
input terminal.
L3
L2
L1
GND
.