Juniper QFabric QFX3000-G Hardware Documentation page 109

Hide thumbs Also See for QFabric QFX3000-G:
Table of Contents

Advertisement

Copyright © 2018, Juniper Networks, Inc.
The QFX3008-I Interconnect device has six power supplies and two wiring trays in a
QFX3008-I Interconnect device. Power supplies are installed at the rear bottom of the
chassis in slots
through
0
5
trays are installed at the rear bottom of the chassis on either side of the power supplies.
The wiring tray in slot
Wiring Tray 0
through
. The wiring tray in slot
0
2
in slots
through
.
3
5
WARNING:
The chassis is pluggable type A equipment installed in a
restricted-access location. It has a separate protective earthing terminal
provided on the chassis. This separate protective earthing terminal must be
permanently connected to earth ground.
CAUTION:
Mixing different types of wiring trays in the same chassis is not a
supported configuration.
The single-phase wiring tray has three appliance inlets. See
for a QFX3008-I Interconnect Device with Single-Phase Wiring Trays" on page
NOTE:
To provide power feed redundancy, all three appliance inlets on the
single-phase wiring tray in slot
power feeds derived from feed A, and all appliance inlets on the wiring tray
in slot
Wiring Tray 1
feed B. This configuration provides the commonly deployed A/B feed
redundancy for the system.
The three-phase wiring trays have a terminal block specific to either standard delta or
standard wye wiring configurations. The power cords that you provide for the three-phase
wiring trays must be installed before you install the wiring trays. See
Specifications for a QFX3008-I Interconnect Device with Three-Phase Delta Wiring Trays"
on page 282
and
"AC Power Specifications for a QFX3008-I Interconnect Device with
Three-Phase Wye Wiring Trays" on page
NOTE:
To provide power feed redundancy, the three-phase wiring tray in slot
must be powered by a dedicated power feed derived from feed A,
Wiring Tray 0
and the wiring tray in slot
feed derived from feed B. This configuration provides the commonly deployed
A/B feed redundancy for the system.
You must install two wiring trays in a QFX3008-I Interconnect device. Wiring trays are
installed at the bottom of the chassis in slots labeled
to right). See
"Slot Numbering for a QFX3008-I Interconnect Device" on page
(left to right when viewed from the rear of the chassis). Wiring
provides input power to the power supplies in slots
provides input power to the power supplies
Wiring Tray 1
Wiring Tray 0
must be powered by dedicated power feeds derived from
282.
Wiring Tray 1
must be powered by a dedicated power
Chapter 3: QFX3008-I Overview
"AC Power Specifications
281.
must be powered by dedicated
"AC Power
and
Wiring Tray 0
Wiring Tray 1
44.
(left
59