Clearance Requirements for Airflow and Hardware Maintenance for a QFX3500 Device
250
If you are mounting a QFX3600 or QFX3600-I device in a rack or cabinet with other
equipment, ensure that the exhaust from other equipment does not blow into the
intake vents of the chassis.
Leave at least 24 in. (61 cm) both in front of and behind the QFX3600 or QFX3600-I
device. For service personnel to remove and install hardware components, you must
leave adequate space at the front and back of the device. NEBS GR-63 recommends
that you allow at least 30 in. (76.2 cm) in front of the rack or cabinet and 24 in. (61 cm)
behind the rack or cabinet.
Rack Requirements for a QFX3600 or QFX3600-I Device on page 233
Cabinet Requirements for a QFX3600 or QFX3600-I Device on page 241
General Site Guidelines on page 217
Rack-Mounting and Cabinet-Mounting Warnings on page 343
When planning the site for installing a QFX3500 device, you must allow sufficient
clearance around the installed chassis (see
Figure 135: Clearance Requirements for Airflow and Hardware Maintenance for a QFX3500
Device
Clearance required
for maintenance
24 in. (60.9 cm)
Front
19 in.
(48.26 cm)
For the cooling system to function properly, the airflow around the chassis must be
unrestricted. See
"Cooling System and Airflow for a QFX3500 Device" on page 124
more information about the airflow through the chassis.
If you are mounting a QFX3500 device in a rack or cabinet with other equipment, ensure
that the exhaust from other equipment does not blow into the intake vents of the
chassis.
Leave at least 24 in. (61 cm) both in front of and behind the QFX3500 device. For
service personnel to remove and install hardware components, you must leave adequate
space at the front and back of the device. NEBS GR-63 recommends that you allow
Figure 135 on page
250).
31 in.
(78.7 cm)
Copyright © 2018, Juniper Networks, Inc.
Clearance required
for maintenance
24 in. (60.9 cm)
Rear
17.4 in.
(44.2 cm)