Table 71: QFX3100 Director Device Environmental Tolerances

Description
Altitude
Relative humidity
Temperature
Related
Documentation
Environmental Requirements and Specifications for a QFX3008-I Interconnect Device
Copyright © 2018, Juniper Networks, Inc.
Maintain ambient airflow for normal device operation. If the airflow is blocked or
restricted, or if the intake air is too warm, the device might overheat, leading to the
device temperature monitor shutting down the device to protect the hardware
components.
Table 71 on page 219
provides the required environmental conditions for normal device
operation.
Tolerance
No performance degradation to 10,000 feet (3048 meters)
Normal operation ensured in relative humidity range of 5% through 85%, noncondensing
Normal operation ensured in temperature range of 32° F through 104° F (0° C through 40° C)
Short-term operation ensured in temperature range of 23° F through 131° F (–5° C through
55° C)
NOTE:
As defined in NEBS GR-63-CORE, Issue 3, short-term events can be up to 96 hours in
duration but not more than 15 days per year.
Nonoperating storage temperature in shipping container: –40° F through 158° F (–40° C through
70° C)
NOTE:
Install QFX Series devices only in restricted areas, such as dedicated
equipment rooms and equipment closets, in accordance with Articles 110-16,
110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70.
Clearance Requirements for Airflow and Hardware Maintenance for a QFX3100 Director
Device on page 245
Installing and Connecting a QFX3100 Director Device on page 377
The QFX3008-I Interconnect device chassis must be installed in a rack or cabinet housed
in a dry, clean, well-ventilated, and temperature-controlled environment.
Follow these environmental guidelines:
The site must be as dust-free as possible, because dust can clog air intake vents and
filters, reducing the efficiency of the device cooling system.
Maintain ambient airflow for normal device operation. If the airflow is blocked or
restricted, or if the intake air is too warm, the device might overheat, leading to the
device temperature monitor shutting down the device to protect the hardware
components.