Figure 130: Airflow Through the Front Card Cage and Powerhouse

The air intake to cool the rear card cage is located on the front sides of the chassis.
Cool air is pulled in through the side fan trays. Hot air exhausts from the Control Boards
and rear cards.

Figure 131: Airflow Through the Rear Card Cage

If you are mounting the device on a rack or cabinet along with other equipment, ensure
that the exhaust from other equipment does not blow into the intake vents of the
chassis.
Leave at least 24 in. (61 cm) both in front of and behind the switch. Allow at least 6 in.
(15.2 cm) of clearance on each side of the chassis. Leave adequate space at the front
of the switch for service personnel to remove and install hardware components. NEBS
GR-63 recommends that you allow at least 30 in. (76.2 cm) in front of the rack or
cabinet and 24 in. (61 cm) behind the rack or cabinet. See
Chapter 10: Rack and Cabinet Requirements
Figure 132 on page
248.