Table 110: Three-Phase Delta Ac Power Cord Specifications - Juniper QFabric QFX3000-G Hardware Documentation

Hide thumbs Also See for QFabric QFX3000-G:
Table of Contents

Advertisement

Table 110: Three-Phase Delta AC Power Cord Specifications

Electrical
Rating
Plug Type
400 VAC, 32 A
International
Electrotechnical
Commission (IEC) 60309
Related
Documentation
Copyright © 2018, Juniper Networks, Inc.
WARNING:
The QFX3008-I Interconnect device is pluggable type A equipment
installed in a restricted-access location. It has a separate protective earthing
terminal provided on the chassis in addition to the grounding pin of the power
supply cord. This separate protective earthing terminal must be permanently
connected to earth.
CAUTION:
Power cords and cables must not block access to device
components or drape where people could trip on them.
Each three-phase AC wiring tray has a metal wiring compartment that contains the AC
terminal block and ground. There are two types of three-phase wiring trays: delta
(three-wire) and wye (four-wire). The wye AC terminal block consists of four input
terminals labeled
N
,
L1
,
L2
, and
convention.
You must provide cords appropriate for your geographical location. The AC power cord
wires insert into the AC terminal block on the wiring tray.
The power cords you provide must comply with the specifications listed in
Table 110 on page
287.
NOTE:
In North America, AC power cords must not exceed 4.5 m
(approximately 14.75 ft) in length, to comply with National Electrical Code
(NEC) Sections 400-8 (NFPA 75, 5-2.2) and 210-52, and Canadian Electrical
Code (CEC) Section 4-010(3).
Plug
Color
Red
AC Power Supply in a QFX3008-I Interconnect Device on page 56
Wiring Tray in a QFX3008-I Interconnect Device on page 58
AC Power Electrical Safety Guidelines on page 362
AC Power Disconnection Warning on page 363
General Electrical Safety Guidelines and Warnings on page 359
Chapter 14: Planning QFX3008-I Power Requirements
L3
, from top to bottom in the common three-phase naming
Cord or Cable Type
The cord or cable must be HAR compliant, IEC 60245 (designation
60245 IEC 53) or IEC 60227 (designation 60227 IEC 53); or meet
one of the following standards (North America): SV, SVE, SVO,
SVOO, SVT, SVTO, SVTOO, SP-2, SPE-2, SPT-2, NISP-2, NISPE-2,
NISPT-2, SP-3, SPE-3, SPT-3, SJ, SJE, SJO, SJOO, SJT, SJTO,
SJTOO, S, SE, SO, SOO, ST, STO, STOO
287