L7: Torque Limit; L8: Drive Protection - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
L6-06
Torque Detection Time 2
(04A6)
L6-13
Motor Underload Curve
Select
(062E)
L6-14
Motor Underload Level
@ Min Freq
(062F)

L7: Torque Limit

No.
Name
(Hex.)
L7-01
Forward Torque Limit
(04A7)
RUN
L7-02
Reverse Torque Limit
(04A8)
RUN
L7-03
Forward Regenerative
Trq Limit
(04A9)
RUN
L7-04
Reverse Regenerative Trq
Limit
(04AA)
RUN
L7-16
Torque Limit Process at
Start
(044D)

L8: Drive Protection

No.
Name
(Hex.)
L8-02
Overheat Alarm Level
(04AE)
L8-03
Overheat Pre-Alarm
Selection
(04AF)
L8-05
Input Phase Loss
Protection Sel
(04B1)
L8-07
Output Phase Loss
Protection Sel
(04B3)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Description
V/f
OLV/PM EZOLV
OLV/PM
Sets the detection time for Overtorque/Undertorque Detection 2.
V/f
OLV/PM EZOLV
OLV/PM
Sets the motor underload protection (UL6 [Undertorque Detection 6]) based on motor load
and sets the level of L6-02 [Torque Detection Level 1] to refer to Fbase or Fmax.
0 : Base Frequency Enable
1 : Max Frequency Enable
V/f
OLV/PM EZOLV
OLV/PM
Sets the UL6 [Undertorque Detection 6] detection level at minimum frequency by
percentage of drive rated current.
Description
V/f
OLV/PM EZOLV
OLV/PM
Sets the torque limit value for forward motoring as a percentage, where motor rated torque
is the 100% value.
V/f
OLV/PM
OLV/PM EZOLV
Sets the torque limit value for reversed motoring as a percentage, where motor rated torque
is the 100% value.
V/f
OLV/PM EZOLV
OLV/PM
Sets the torque limit value for forward regenerative conditions as a percentage of the motor
rated torque.
V/f
OLV/PM EZOLV
OLV/PM
Sets the torque limit value for reversed regenerative conditions as a percentage of the
motor rated torque.
V/f
OLV/PM EZOLV
OLV/PM
Assigns a time filter to allow the torque limit to build at start.
0 : Disabled
1 : Enabled
Description
V/f
OLV/PM EZOLV
OLV/PM
Sets the oH detection level temperature.
V/f
OLV/PM
OLV/PM EZOLV
Sets drive operation if it detects an oH alarm.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Operate at Reduced Speed (L8-19)
V/f
OLV/PM EZOLV
OLV/PM
Sets the function to enable and disable input phase loss detection.
0 : Disable
1 : Enabled
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to enable and disable output phase loss detection. The drive starts output
phase loss detection when the output current decreases to less than 5% of the drive rated
current.
Note:
The drive can incorrectly start output phase loss detection in these conditions:
• The motor rated current is very small compared to the drive rating.
• The drive is operating a PM motor with a small load.
0 : Disabled
1 : Fault when one phase is lost
2 : Fault when two phases are lost
1.11 L: Protection Functions
Default
Ref.
(Range)
0.1 s
380
(0.0 - 10.0 s)
0
380
(0, 1)
15%
381
(0 - 300%)
Default
Ref.
(Range)
200%
382
(0 - 300%)
200%
382
(0 - 300%)
200%
382
(0 - 300%)
200%
382
(0 - 300%)
1
383
(0, 1)
Default
Ref.
(Range)
Determined by o2-04
383
(50 - 150 °C)
4
383
(0 - 4)
1
384
(0, 1)
1
384
(0 - 2)
1
83