YASKAWA HV600 Manual page 164

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.2 A: Initialization Parameters
Note:
After the drive does an HVAC Initialization, the keypad will show H1-03, H1-04, H1-05 and H2-03 in the Modified Parameters list.
The drive will not initialize the parameters in
Table 2.2 Parameters that are not Initialized Using a 2-Wire Sequence or a 3-Wire Sequence
No.
A1-00
A1-02
A1-07
E1-03
E5-01
E5-02
E5-03
E5-04
E5-05
E5-06
E5-07
E5-09
E5-24
F6-08
F6-xx/F7-xx
L8-35
o2-04
o2-24
q1-xx - q8-xx
r1-xx
Note:
• Set A1-06 [Application Preset] to let the drive automatically set the best parameter settings for the selected application. The drive does not
initialize A1-02 when A1-03 = 2220, 3330.
• When A1-03 = 2220, 3330, the drive automatically sets A1-05 [Password Setting] = 0000. Make sure that you set the password again for
applications where a password is necessary.
A1-04: Password
No.
Name
(Hex.)
A1-04
Password
(0104)
If the password entered in A1-04 does not agree with the password setting in A1-05, you cannot change these
parameters:
• A1-01 [Access Level Selection]
• A1-02 [Control Method Selection]
• A1-03 [Initialize Parameters]
• A1-06 [Application Preset]
• A1-07 [DriveWorksEZ Function Selection]
• A2-01 to A2-32 [User Parameter 1 to 32]
164
Table 2.2
when A1-03 = 2220, 3330.
Language Selection
Control Method Selection
DriveWorksEZ Function Selection
V/f Pattern Selection
PM Motor Code Selection
PM Motor Rated Power (kW)
Motor Rated Current (FLA)
PM Motor Pole Count
PM Motor Resistance (ohms/phase)
PM d-axis Inductance (mH/phase)
PM q-axis Inductance (mH/phase)
PM Back-EMF Vpeak (mV/(rad/s))
PM Back-EMF L-L Vrms (mV/rpm)
Comm Parameter Reset @Initialize
Communication Option Parameters
Set F6-08 = 1 [Comm Parameter Reset @Initialize = Reset Back to Factory Default] to initialize communication option
card parameters.
Installation Method Selection
Drive Model (KVA) Selection
LED Light Function Selection
DriveWorksEZ Parameters
DWEZ Connection 1-20
V/f
OLV/PM EZOLV
OLV/PM
Entry point for the password set in A1-05 [Password Setting]. The user can view the settings of
parameters that are locked without entering the password. Enter the correct password in this
parameter to change parameter settings.
Name
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
0000
(0000 - 9999)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents