ON : The output frequency > L4-03.
OFF : The output frequency < "L4-03 - L4-04", or the output frequency ≤ L4-03.
L4-03:
Figure 2.68 Example of Frequency Detection 4 (Value of L4-03 is Positive)
17: Torque Detection 1 (N.C.)
Setting Value
Function
17
Torque Detection 1 (N.C.)
Use the L6 [Torque Detection] parameters to set torque detection.
OFF : The output current/torque > L6-02 [Torque Detection Level 1], or the output current/torque <
L6-02 for longer than the time set in L6-03 [Torque Detection Time 1].
Note:
• When L6-01 ≥ 5, the drive will detect when the output current/torque is less than L6-02 for longer than L6-03.
• Refer to
L6: Torque Detection on page 375
18: Torque Detection 2 (N.O.)
Setting Value
Function
18
Torque Detection 2 (N.O.)
Use the L6 [Torque Detection] parameters to set torque detection.
ON : The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque < L6-
05 for longer than the time set in L6-06 [Torque Detection Time 2].
Note:
• When L6-04 ≥ 5, the drive will detect when the output current/torque is less than L6-05 for longer than L6-06.
• Refer to
L6: Torque Detection on page 375
19: Torque Detection 2 (N.C.)
Setting Value
Function
19
Torque Detection 2 (N.C.)
Use the L6 [Torque Detection] parameters to set torque detection.
OFF : The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque <
L6-05 for longer than the time set in L6-06 [Torque Detection Time 2].
Note:
• When L6-04 ≥ 5, the drive will detect when the output current/torque is less than L6-05 for longer than L6-06.
• Refer to
L6: Torque Detection on page 375
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive detects overtorque or undertorque.
for more information.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects overtorque or undertorque.
for more information.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive detects overtorque or undertorque.
for more information.
L4-04:
Description
Description
Description
2.8 H: Terminal Functions