1.11 L: Protection Functions
No.
Name
(Hex.)
L6-10
Mech Fatigue Detect Delay
Time
(046A)
L6-11
Mech Fatigue Hold Off Time
(046B)

L7: Torque Limit

No.
Name
(Hex.)
L7-01
Forward Torque Limit
(04A7)
RUN
L7-02
Reverse Torque Limit
(04A8)
RUN
L7-03
Forward Regenerative Trq
Limit
(04A9)
RUN
L7-04
Reverse Regenerative Trq
Limit
(04AA)
RUN
L7-06
Torque Limit Integral Time
(04AC)
L7-07
Torque Limit during Accel/
Decel
(04C9)
L7-16
Torque Limit Process at Start
(044D)

L8: Drive Protection

No.
Name
(Hex.)
L8-01
3% ERF DB Resistor
Protection
(04AD)
L8-02
Overheat Alarm Level
(04AE)
L8-03
Overheat Pre-Alarm
Selection
(04AF)
L8-05
Input Phase Loss Protection
Sel
(04B1)
88
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the time for mechanical deterioration detection.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the time that the drive will start mechanical deterioration detection triggered by the cumulative
operation time of the drive.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the torque limit value for forward motoring as a percentage, where motor rated torque is the
100% value.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the torque limit value for reversed motoring as a percentage, where motor rated torque is the
100% value.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the torque limit value for forward regenerative conditions as a percentage of the motor rated
torque.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the torque limit value for reversed regenerative conditions as a percentage of the motor rated
torque.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the integral time constant for the torque limit function.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the torque limit function during acceleration and deceleration.
0 : Proportional only
1 : Proportional & Integral control
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Assigns a time filter to allow the torque limit to build at start.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function to enable braking resistor protection with a Yaskawa ERF series braking resistor
(3% ED) installed on the heatsink.
0 : No
1 : Yes
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the oH detection level in temperature.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets operation after the drive detects an oH alarm.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Operate at Reduced Speed (L8-19)
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to enable and disable input phase loss detection.
0 : Disabled
1 : Enabled
Description
Description
Description
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
Default
(Range)
0.1 s
(0.0 - 10.0 s)
0 h
(0 - 65535 h)
Default
(Range)
200%
(0 - 300%)
200%
(0 - 300%)
200%
(0 - 300%)
200%
(0 - 300%)
200 ms
(5 - 10000 ms)
0
(0, 1)
1
(0, 1)
Default
(Range)
0
(0, 1)
Determined by o2-04, C6-01
(50 - 150 °C)
3
(0 - 4)
Determined by o2-04
(Determined by o2-04)

Advertisement

Table of Contents
loading

Table of Contents