Item
Applicable options
Number of connected drives
Communication Specifications
Commands/responses
Synchronous control
Note:
• The communication speed in gateway mode is slower than the speed in fieldbus communications. Make sure that the speed is acceptable for
your system.
• Response speed with the communication option is slower than the speed with point-to-point communications.
• Set H5-03 [Communication Parity Selection] to the same value on the master drive and slave drives.
WARNING! Injury to Personnel. Separately prepare safety protection equipment and systems, for example fast stop switches. If the
motor does not stop correctly from the disconnection of communications cable or electrical interference, it can cause serious injury.
Configuring Gateway Mode
Table 2.42
shows sample settings to connect 4 slave drives:
F6-16
[Gateway Mode]
Drive 0
*2
1 - 4
(Master Drive)
Drive 1
0
(Slave drive)
Drive 2
0
(Slave drive)
Drive 3
0
(Slave drive)
Drive 4
0
(Slave drive)
*1
Restart the drive to apply the new settings.
*2
Specify the number of slave drives you will connect.
*3
Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
*4
Set a slave address that is different from other slave devices.
*5
Enter the same value that you use for the master drive.
*6
To correctly detect the response timeout, do not change the value of H5-06 from the default value.
*7
Set H5-09 ≥ 0.9. When H5-09 < 0.9, the drive will detect CE [Modbus Communication Error] before it detects a response timeout.
*8
On each slave drive, set b1-01 [Frequency Reference Selection 1] and b1-02 [Run Command Selection 1] to 2 [Serial Communications].
Gateway Mode Overview
In gateway mode, the drive operates as shown in
A - Controller
B - Communication Option
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Table 2.41 Specification
All the options that support the MEMOBUS access function (for example, PROFINET, EtherNet/IP, etc.)
Maximum: 5 units
MEMOBUS/Modbus (RTUmode) communications
The controller can send this data to each drive (Drive 0 to Drive 4):
• Control commands: Run commands and frequency references
• Control responses: Output frequency and drive status (during run, faults)
• Read and write parameters
• Read monitors
Not supported
Table 2.42 Sample Settings for Using Gateway Mode
H5-02
[Communication
H5-01
Speed Selection]
[Drive Node
H5-03
*1
Address]
[Communication
Parity Selection]
*5
1F (Default)
*3 *4
*5
01
*3 *4
*5
02
*3 *4
*5
03
*3 *4
*5
04
Table
2.43.
Specification
H5-06
H5-09
[Drive Transmit
[CE Detection
Wait Time]
Time]
5 ms (factory
*7
≥ 2.0 s
*6
default)
5 ms (factory
*7
≥ 0.9 s
*6
default)
5 ms (factory
*7
≥ 0.9 s
*6
default)
5 ms (factory
*7
≥ 0.9 s
*6
default)
5 ms (factory
*7
≥ 0.9 s
*6
default)
C - Master Drive (Drive 0)
D - Slave Drives (Drives 1 to 4)
2.7 F: Options
b1-01
b1-02
[Frequency
[Run Command
Reference
Selection 1]
Selection 1]
3 [Option PCB]
3 [Option PCB]
2 [Serial
2 [Serial
*8
Communications]
Communications]
2 [Serial
2 [Serial
*8
Communications]
Communications]
2 [Serial
2 [Serial
*8
Communications]
Communications]
2 [Serial
2 [Serial
*8
Communications]
Communications]
265
*8
*8
*8
*8
2