2.14 Y: Application Features
Y1-21: Prime Loss Activation Freq
No.
Name
(Hex.)
Y1-21
Prime Loss Activation Freq
(3C14)
Y1-22: Prime Loss Selection
No.
Name
(Hex.)
Y1-22
Prime Loss Selection
(3C15)
0 : Fault (and Digital Output)
The keypad shows an LOP [Loss of Prime] fault and the motor coasts to stop. The output terminal set for H2-xx = 94
[MFDO Function Selection = Loss of Prime] will activate.
To deactivate the digital output, do a Fault Reset.
1 : Alarm (and Digital Output)
The keypad shows an LOP [Loss of Prime] alarm and the output terminal set for H2-xx = 94 will activate.
2 : Digital Output Only
The output terminal set for H2-xx = 94 will activate.
Y1-23: Prime Loss Max Restart Time
No.
Name
(Hex.)
Y1-23
Prime Loss Max Restart
Time
(3C16)
Y1-40: Maximum Speed
No.
Name
(Hex.)
Y1-40
Maximum Speed
(3C27)
RUN
Note:
This parameter is not effective when Y1-40 = 0.0 Hz or Y1-40 > E1-04 [Maximum Output Frequency] × d2-01 [Frequency Reference Upper
Limit].

Y2: PID Sleep and Protection

Sleep Function
The Sleep Function uses the monitor data set in Y2-01 [Sleep Level Type] to know if the drive is necessary in the
system and turn off the drive.
This function helps to save the energy and prevent the deterioration on the motor.
Sleep Activation Level and Sleep Level
• Sleep Activation Level:
This level sets when the Sleep Function should start operation. You can use Y2-04 [Sleep Activation Level] or
Minimum Speed (the largest value from d2-02, Y1-06, and Y4-12) to set this level.
When the output frequency increases to more than the Sleep Activation Level, the Sleep Function will start to
monitor the system.
• Sleep Level:
This is the level that the drive uses to go to sleep (stop). You can use Y2-02 [Sleep Level] or Minimum Speed to set
this level.
472
V/f
OLV/PM EZOLV
OLV/PM
Sets the frequency level above which the drive enables Loss of Prime detection.
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive response when the drive is in the Loss of Prime condition.
V/f
OLV/PM EZOLV
OLV/PM
Sets the time in minutes that the drive will wait before it tries a restart after a restart fails or after it
does not do a restart because of a fault.
V/f
OLV/PM
OLV/PM EZOLV
Sets the maximum speed.
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
0.0 Hz
(0.0 - 400.0)
Default
(Range)
0
(0 - 2)
Default
(Range)
0.2 min
(0.2 - 6000.0 min)
Default
(Range)
0.0 Hz
(Determined by A1-02)