L5: Fault Restart

No.
Name
(Hex.)
L5-01
Number of Auto-Restart
Attempts
(049E)
L5-02
Fault Contact at Restart
Select
(049F)
L5-04
Interval Method Restart
Time
(046C)
L5-07
Fault Reset Enable Select
Grp1
(0B2A)
L5-08
Fault Reset Enable Select
Grp2
(0B2B)
L5-40
Low Feedback Flt Retry
Selection
(3670)
L5-41
Hi Feedback Flt Retry
Selection
(3671)
L5-42
Feedback Loss Fault
Retry Select
(3672)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the number of times that the drive will try to restart.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function that sends signals to the MFDO terminal set for Fault [H2-xx = E] while
the drive is automatically restarting.
0 : Active Only when Not Restarting
1 : Always Active
V/f
OLV/PM EZOLV
OLV/PM
Sets the time interval between each Auto Restart attempt.
V/f
OLV/PM EZOLV
OLV/PM
Use these 4 digits to set the Auto Restart function for oL1 to oL4. From left to right, the
digits set oL1, oL2, oL3, and oL4, in order.
0000 : Disabled
0001 : Enabled (—/—/—/oL4)
0010 : Enabled (—/—/oL3/—)
0011 : Enabled (—/—/oL3/oL4)
0100 : Enabled (—/oL2/—/—)
0101 : Enabled (—/oL2/—/oL4)
0110 : Enabled (—/oL2/oL3/—)
0111 : Enabled (—/oL2/oL3/oL4)
1000 : Enabled (oL1/—/—/—)
1001 : Enabled (oL1/—/—/oL4)
1010 : Enabled (oL1/—/oL3/—)
1011 : Enabled (oL1/—/oL3/oL4)
1100 : Enabled (oL1/oL2/—/—)
1101 : Enabled (oL1/oL2/—/oL4)
1110 : Enabled (oL1/oL2/oL3/—)
1111 : Enabled (oL1/oL2/oL3/oL4)
V/f
OLV/PM
OLV/PM EZOLV
Use these 4 digits to set the Auto Restart function for Uv1, ov, oH1, and GF. From left to
right, the digits set Uv1, ov, oH1, and GF, in order.
0000 : Disabled
0001 : Enabled (—/–/—/GF)
0010 : Enabled (—/–/oH1/–)
0011 : Enabled (—/–/oH1/GF)
0100 : Enabled (—/ov/—/–)
0101 : Enabled (—/ov/—/GF)
0110 : Enabled (—/ov/oH1/–)
0111 : Enabled (—/ov/oH1/GF)
1000 : Enabled (Uv1/–/—/–)
1001 : Enabled (Uv1/–/—/GF)
1010 : Enabled (Uv1/–/oH1/–)
1011 : Enabled (Uv1/–/oH1/GF)
1100 : Enabled (Uv1/ov/—/–)
1101 : Enabled (Uv1/ov/—/GF)
1110 : Enabled (Uv1/ov/oH1/–)
1111 : Enabled (Uv1/ov/oH1/GF)
V/f
OLV/PM
OLV/PM EZOLV
Sets the drive to do an Auto Restart when the drive detects an LFB [Low Feedback
Sensed] fault.
0 : No Retry
1 : Retry
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive to do an Auto Restart when the drive detects an HFB [High Feedback
Sensed] fault.
0 : No Retry
1 : Retry
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive to try an Auto Restart when it drive detects an FDBKL [WIRE Break] fault.
0 : No Retry
1 : Retry
1.11 L: Protection Functions
Default
Ref.
(Range)
0
370
(0 - 10 times)
0
370
(0, 1)
10.0 s
371
(0.5 - 3600.0 s)
1111
371
(0000 - 1111)
1111
372
(0000 - 1111)
0
372
(0, 1)
0
373
(0, 1)
0
374
(0, 1)
1
81