2.8 H: Terminal Functions
12: Forward Jog
Setting Value
Function
12
Forward Jog
Note:
• It is not necessary to input the Run command.
• The Forward JOG command has priority over all other frequency references.
• When the Forward JOG and Reverse JOG commands are activated at the same time for 500 ms or longer, the drive will ramp to stop.
13: Reverse Jog
Setting Value
Function
13
Reverse Jog
Note:
• It is not necessary to input the Run command.
• The Reverse JOG command has priority over all other frequency references.
• When the Forward JOG and Reverse JOG commands are activated at the same time for 500 ms or longer, the drive will ramp to stop.
14: Fault Reset
Setting Value
Function
14
Fault Reset
If the drive detects a fault, the drive will activate the fault relay output, turn off the output, and the motor will coast to
stop.
If the drive detects a fault for which you can set the stopping method, apply the appropriate Stopping Method. Then
push
(RESET) on the keypad to turn the Run command OFF, or activate the fault reset terminal to reset the fault.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before trying to reset a fault.
15: Fast Stop (N.O.)
Setting Value
Function
15
Fast Stop (N.O.)
If you cancel the fast stop input, the drive will not restart the motor until you meet these conditions:
• Fully stop the motor
• Cancel the Run command
• Cancel the fast stop command
288
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to operate the motor in the forward direction at the Jog Frequency set in d1-17 [Jog Reference].
Figure 2.51 JOG Operation Pattern
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to operate the motor in the reverse direction at the Jog Frequency set in d1-17 [Jog Reference].
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to reset the current fault when the Run command is inactive.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is activated while
the drive is operating.
Description
Description
Description
Description