b2-04: DC Inject Braking Time at Stop
No.
Name
(Hex.)
b2-04
DC Inject Braking Time at
Stop
(018C)
This function fully stops a motor with a large inertia during deceleration and will not let the inertia continue to rotate
the motor.
Set this parameter to 0.00 to disable the function.
When a longer time is necessary to stop the motor, increase the value.
b2-09: Pre-heat Current 2
No.
Name
(Hex.)
b2-09
Pre-heat Current 2
(01E1)
b2-12: Short Circuit Brake Time @ Start
No.
Name
(Hex.)
b2-12
Short Circuit Brake Time @
Start
(01BA)
This function stops and restarts a coasting PM motor. The drive short circuits all the three motor phases to make
braking torque in the motor.
Set this parameter to 0.00 to disable the function.
Note:
Short circuit Braking will let external forces rotate the PM motor. Use DC Injection Braking to prevent motor rotation from external forces.
b2-13: Short Circuit Brake Time @ Stop
No.
Name
(Hex.)
b2-13
Short Circuit Brake Time @
Stop
(01BB)
This function fully stops a PM motor with a large inertia during deceleration and will not let the inertia continue to
rotate the motor.
Short Circuit Braking operates for the time set in b2-13 when output frequency is less than the value set in b2-01 [DC
Injection/Zero SpeedThreshold] or E1-09 [Minimum Output Frequency].
Set this parameter to 0.00 to disable the function.
b2-18: Short Circuit Braking Current
No.
Name
(Hex.)
b2-18
Short Circuit Braking
Current
(0177)
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor rated current.
• A1-02 = 5 [OLV/PM]: E5-03 [PM Motor Rated Current (FLA)]
• A1-02 = 8 [EZOLV]: E9-06 [Motor Rated Current (FLA)]
The Short Circuit Braking current cannot be higher than the drive rated current, although you can use b2-18 to set a
higher current level. The maximum rated current is 120%.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the DC Injection Braking Time at stop.
V/f
OLV/PM EZOLV
OLV/PM
Sets the percentage of motor rated output current used for the motor pre-heat function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the Short Circuit Braking time at start.
V/f
OLV/PM EZOLV
OLV/PM
Sets the Short Circuit Braking time at stop.
V/f
OLV/PM EZOLV
OLV/PM
Sets the Short Circuit Braking Current as a percentage of the motor rated current.
Description
Description
Description
Description
Description
2.3 b: Application
Default
(Range)
0.00 s
(0.00 - 10.00 s)
Default
(Range)
5%
(0 - 100%)
Default
(Range)
0.00 s
(0.00 - 25.50 s)
Default
(Range)
Determined by A1-02
(0.00 - 25.50 s)
Default
(Range)
100.0%
(0.0 - 200.0%)
2
189