YASKAWA HV600 Manual page 502

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.14 Y: Application Features
YF-15: PI Aux Level Detect Restart Time
No.
Name
(Hex.)
YF-15
PI Aux Level Detect Restart
Time
(3F5E)
YF-16: PI Auxiliary Control P Gain
No.
Name
(Hex.)
YF-16
PI Auxiliary Control P Gain
(3F5F)
RUN
YF-17: PI Auxiliary Control I Time
No.
Name
(Hex.)
YF-17
PI Auxiliary Control I Time
(3F60)
RUN
Note:
Set this parameter to 0.0 to disable the integrator.
YF-18: PI Aux Control Detect Time Unit
No.
Name
(Hex.)
YF-18
PI Aux Control Detect Time
Unit
(3F61)
0 : Minutes (min)
1 : Seconds (sec)
YF-19: PI Aux Ctrl Feedback WireBreak
No.
Name
(Hex.)
YF-19
PI Aux Ctrl Feedback
WireBreak
(3F62)
0 : Disabled
1 : Alarm Only
The keypad will show an AUXFB [PI Aux Feedback Level Loss] alarm.
2 : Fault (no retry, coast to stop)
When the drive is in AUTO, HAND, or Sleep mode, the keypad will show an AUXFB [PI Aux Feedback Level Loss]
fault.
Note:
If the drive has not received a Run command, the keypad will only show an AUXFB alarm.
YF-20: PI Aux Main PI Speed Control
No.
Name
(Hex.)
YF-20
PI Aux Main PI Speed
Control
(3F63)
502
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time the drive will wait before it tries an Auto-Restart of LOAUX [Low PI Aux
Feedback Level] or HIAUX [High PI Aux Feedback Level] fault.
V/f
OLV/PM
OLV/PM EZOLV
Sets the proportional gain for the suction pressure control.
V/f
OLV/PM
OLV/PM EZOLV
Sets the integral time for the suction pressure control.
V/f
OLV/PM
OLV/PM EZOLV
Sets the time unit for YF-10 [PI Aux Control Low Lvl Det Time] and YF-13 [PI Aux High Level
Detection Time].
V/f
OLV/PM EZOLV
OLV/PM
Sets how the analog input selected for PI Aux Feedback will respond when it is programmed to
receive a 4 mA to 20 mA signal and the signal is lost.
V/f
OLV/PM EZOLV
OLV/PM
Sets if the PI Auxiliary Controller has an effect on output speed.
Description
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
5.0 min
(0.1 - 6000.0 min)
Default
(Range)
2.00
(0.00 - 25.00)
Default
(Range)
5.0 s
(0.0 - 360.0 s)
Default
(Range)
1
(0, 1)
Default
(Range)
2
(0 - 2)
Default
(Range)
1
(0, 1)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents