YASKAWA HV600 Manual page 66

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

1.10 H: Terminal Functions
Setting Value
Function
10E
!Fault
110
!Alarm
111
!Fault Reset Command
Active
112
!Timer Output
113
!Speed Agree 2
114
!User-Set Speed Agree 2
115
!Frequency Detection 3
116
!Frequency Detection 4
117
!Torque Detection 1 (N.
C.)
118
!Torque Detection 2 (N.
O.)
119
!Torque Detection 2 (N.
C.)
11A
!During Reverse
11B
!During Baseblock (N.C.)
11C
!Motor 2 Selected
66
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive detects a fault.
Note:
The terminal will not deactivate for CPF00 and CPF01 [Control Circuit Error] faults.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the drive detects a minor fault.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the drive receives the Reset command from the control circuit terminal, serial
communications, or the communication option.
V/f
OLV/PM
OLV/PM EZOLV
Use this setting when the drive uses the timer function as an output terminal.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree
Detection Width (+/-)].
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is not in the range of "frequency reference ± L4-04".
OFF : The output frequency is in the range of "frequency reference ± L4-04".
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the output frequency is in the range of L4-03 [Speed Agree Detection Level (+/-)] ± L4-
04 [Speed Agree Detection Width (+/-)] and in the range of the frequency reference ± L4-04.
Note:
The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency is not in the range of "L4-03 ± L4-04" or the range of frequency reference ± L4-04.
OFF : The output frequency is in the range of "L4-03 ± L4-04" and the range of frequency reference ± L4-04.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the output frequency > "L4-03 [Speed Agree Detection Level (+/-)] + L4-04 [Speed Agree
Detection Width (+/-)]". After the terminal activates, the terminal stays activated until the output frequency is at the
value of L4-03.
Note:
The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency > "L4-03 + L4-04"
OFF : The output frequency < L4-03, or the output frequency ≤ "L4-03 + L4-04"
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the output frequency > L4-03 [Speed Agree Detection Level (+/-)]. After the terminal
deactivates, the terminal stays deactivated until the output frequency is at the value of "L4-03 - L4-04".
Note:
The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency < "L4-03 - L4-04", or the output frequency ≤ L4-03
OFF : The output frequency > L4-03
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque > L6-02 [Torque Detection Level 1], or the output current/torque < L6-02 for longer
than the time set in L6-03 [Torque Detection Time 1].
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque < L6-05 for longer
than the time set in L6-06 [Torque Detection Time 2].
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque > L6-05 [Torque Detection Level 2], or the output current/torque < L6-05 for longer
than the time set in L6-06 [Torque Detection Time 2].
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the motor operates in the reverse direction.
ON : The motor is operating in the forward direction or the motor stopped.
OFF : The motor is operating in the reverse direction.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates during baseblock. When the drive is in baseblock, the drive output transistor stops switching
and does not make DC bus voltage.
ON : During baseblock.
OFF : The drive is not in baseblock.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when motor 2 is selected.
ON : Motor 1 Selection
OFF : Motor 2 Selection
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Ref.
324
324
324
324
324
324
324
324
324
324
324
324
324
324