Mfdo Setting Values - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.8 H: Terminal Functions
H2-66: Term M5-M6 Secondary Function
No.
Name
(Hex.)
H2-66
Term M5-M6 Secondary
Function
(1B4C)
Expert
H2-67: Terminal M5-M6 Logical Operation
No.
Name
(Hex.)
H2-67
Terminal M5-M6 Logical
Operation
(1B4D)
Expert
Note:
Refer to
Output of Logical Operation Results of MFDO on page 304
logical operations.
H2-68: Terminal M5-M6 Delay Time
No.
Name
(Hex.)
H2-68
Terminal M5-M6 Delay
Time
(1B4E)
Expert

MFDO Setting Values

Selects the function configured to MFDO.
0: During Run
Setting Value
Function
0
During Run
ON : Drive is running
The drive is receiving a Run command or outputting voltage.
OFF : Drive is stopping
1: Zero Speed
Setting Value
Function
1
Zero Speed
Note:
Parameter E1-09 is the reference in all control methods.
308
V/f
OLV/PM
OLV/PM EZOLV
Sets the second function for terminal M5-M6. Outputs the logical calculation results of the terminals
assigned to functions by H2-03 [Terminal M5-M6 Function Select].
V/f
OLV/PM
OLV/PM EZOLV
Sets the logical operation for the functions set in H2-03 [Term M5-M6 Function Selection] and H2-
66 [Term M5-M6 Secondary Function].
V/f
OLV/PM
OLV/PM EZOLV
Sets the minimum on time used to output the logical calculation results from terminal M5-M6.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when you input a Run command and when the drive is outputting voltage.
Figure 2.59 Drive Running Time Chart
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the output frequency < E1-09 [Minimum Output Frequency].
Description
Description
for more information about the relation between parameter settings and
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
F
(0 - FF)
Default
(Range)
0
(0 - 8)
Default
(Range)
0.1 s
(0.0 - 25.0 s)

Hide quick links: