• After Auto-Tuning, the value of E1-13 = E1-05 [Maximum Output Voltage].
• When E1-13 = 0.0, use the value of E1-05 to control the voltage.

E2: Motor Parameters

E2 parameters [Motor Parameters] set induction motor data. To switch drive operation from one motor to another
motor, configure the first motor (motor 1).
Doing Auto-Tuning automatically sets the E2 parameters to the optimal values. If you cannot do Auto-Tuning, set the
E2 parameters manually.
Note:
If you set A1-02 [Control Method Selection] to these control methods, the keypad will not show E2-xx:
• 5 [PM Open Loop Vector]
• 8 [EZ Vector Control]
E2-01: Motor Rated Current (FLA)
No.
Name
(Hex.)
E2-01
Motor Rated Current (FLA)
(030E)
Note:
• If E2-01 < E2-03 [Motor No-Load Current] the drive will detect oPE02 [Parameter Range Setting Error].
• The default settings and setting ranges are in these units:
–0.01 A: 2011 to 2046, 4005 to 4014
–0.1 A: 2059 to 2273, 4021 to 4302
The value set for E2-01 becomes the reference value for motor protection and the torque limit. Enter the motor rated
current as written on the motor nameplate. The value of E2-01 is automatically set to the value input for "Motor Rated
Current" by the Auto-Tuning process.
E2-02: Motor Rated Slip
No.
Name
(Hex.)
E2-02
Motor Rated Slip
(030F)
This parameter value becomes the base slip compensation value. The drive automatically sets this parameter during
Auto-Tuning. When you cannot do Auto-Tuning, calculate the motor rated slip with the information on the motor
nameplate and this formula:
E2-02 = f - (n × p) / 120
• f: Motor rated frequency (Hz)
• n: Rated motor speed (min
• p: Number of motor poles
E2-03: Motor No-Load Current
No.
Name
(Hex.)
E2-03
Motor No-Load Current
(0310)
Note:
The default settings and setting ranges are in these units:
• 0.01 A: 2011 to 2046, 4005 to 4014
• 0.1 A: 2059 to 2273, 4021 to 4302
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the motor rated current in amps.
V/f
OLV/PM EZOLV
OLV/PM
Sets motor rated slip.
-1
(r/min))
V/f
OLV/PM EZOLV
OLV/PM
Sets the no-load current for the motor in amps when operating at the rated frequency and the no-load
voltage.
Description
Description
Description
2.6 E: Motor Parameters
Default
(Range)
Determined by o2-04
(10% to 200% of the drive
rated current)
Default
(Range)
Determined by o2-04
(0.000 - 20.000 Hz)
Default
(Range)
Determined by o2-04
(0 to E2-01)
253
2