YASKAWA HV600 Manual page 338

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.8 H: Terminal Functions
H4-03: Terminal FM Analog Output Bias
No.
Name
(Hex.)
H4-03
Terminal FM Analog Output
Bias
(041F)
RUN
The analog signal output from the FM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with H4-
07 [Terminal FM Signal Level Select].
H4-04: Terminal AM Analog Output Select
No.
Name
(Hex.)
H4-04
Terminal AM Analog Output
Select
(0420)
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-04 = 103 to monitor U1-03 [Output Current].
Note:
• You cannot use all of the monitors in all of the control methods.
• When you use the terminal in through mode, set this parameter to 000 or 031. You can set the terminal AM output level from the PLC
through MEMOBUS/Modbus communications or the communication option.
H4-05: Terminal AM Analog Output Gain
No.
Name
(Hex.)
H4-05
Terminal AM Analog Output
Gain
(0421)
RUN
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with H4-
08 [Terminal AM Signal Level Select].
Example settings:
When the output current of a monitoring item is 100% (drive rated current) in these examples, the voltage of AM
terminal outputs at 5 V (50% of 10 V). Subsequently, the output current at the time the AM terminal outputs a
maximum voltage of 10 V will be 200% of the drive rated current.
• H4-04 = 103 [Terminal AM Analog Output Select = Output Current]
• H4-05 = 50.0%
• H4-06 = 0.0% [Terminal AM Analog Output Bias = 0.0%]
• H4-08 = 0 [0 to 10 V]
H4-06: Terminal AM Analog Output Bias
No.
Name
(Hex.)
H4-06
Terminal AM Analog Output
Bias
(0422)
RUN
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with H4-
08 [Terminal AM Signal Level Select].
H4-07: Terminal FM Signal Level Select
No.
Name
(Hex.)
H4-07
Terminal FM Signal Level
Select
(0423)
338
V/f
OLV/PM EZOLV
OLV/PM
Sets the bias of the monitor signal that is sent from MFAO terminal FM.
V/f
OLV/PM EZOLV
OLV/PM
Sets the monitoring number to be output from the MFAO terminal AM.
V/f
OLV/PM EZOLV
OLV/PM
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
V/f
OLV/PM EZOLV
OLV/PM
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
V/f
OLV/PM EZOLV
OLV/PM
Sets the MFAO terminal FM output signal level.
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
103
(000 - 999)
Default
(Range)
50.0%
(-999.9 - +999.9%)
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
0
(0, 2)