YASKAWA HV600 Manual page 57

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Setting Value
Function
7B
KEB Ride-Thru 2
Activate (N.O.)
7C
Short Circuit Braking (N.
O.)
7D
Short Circuit Braking (N.
C.)
82
PI Switch to Aux
83
Dedicated Multi-Setpoint
YA-02
84
Dedicated Multi-Setpoint
YA-03
85
Dedicated Multi-Setpoint
YA-04
88
Thermostat Fault
90
DWEZ Digital Input 1
91
DWEZ Digital Input 2
92
DWEZ Digital Input 3
93
DWEZ Digital Input 4
94
DWEZ Digital Input 5
95
DWEZ Digital Input 6
96
DWEZ Digital Input 7
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
V/f
OLV/PM
OLV/PM EZOLV
Sets operation of Short Circuit Braking (N.O.).
ON : Short Circuit Braking is enabled.
OFF : Normal operation
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM motor.
V/f
OLV/PM
OLV/PM EZOLV
Sets operation of Short Circuit Braking (N.C.).
ON : Normal operation
OFF : Short Circuit Braking is enabled.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM motor.
V/f
OLV/PM EZOLV
OLV/PM
Sets YF-xx [PI Auxiliary Control] parameters as primary PI loop parameters and disables b5-xx [PID Control].
Note:
When this input is active, YF-xx [PI Auxiliary Control] parameters will always be the primary PI loop parameters.
Parameter YF-20 [PI Aux Main PI Speed Control] does not have an effect.
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to set the PID setpoint to YA-02 [Setpoint 2].
Note:
If you use this function and one of H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2] at the same time, the drive
will detect an oPE03 [Multi-Function Input Setting Err].
ON : YA-02 is PID setpoint.
OFF : YA-01 [Setpoint 1], YA-03 [Setpoint 3], or YA-04 [Setpoint 4] is PID setpoint.
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to set the PID setpoint to YA-03 [Setpoint 3]. Set this function and H1-xx = 83 [Dedicated Multi-
Setpoint YA-02] at the same time.
Note:
If you use this function and one of H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2] at the same time, the drive
will detect an oPE03 [Multi-Function Input Setting Err].
ON : YA-03 is PID setpoint.
OFF : YA-01 [Setpoint 1], YA-02 [Setpoint 2], or YA-04 [Setpoint 4] is PID setpoint.
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to set the PID setpoint to YA-04 [Setpoint 4]. Set this function, H1-xx = 83 [Dedicated Multi-Setpoint
YA-02], and H1-xx = 84 [Dedicated Multi-Setpoint YA-03] at the same time.
Note:
If you use this function and one of H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2] at the same time, the drive
will detect an oPE03 [Multi-Function Input Setting Err].
ON : YA-04 is PID setpoint.
OFF : YA-01 [Setpoint 1], YA-02 [Setpoint 2], or YA-03 [Setpoint 3] is PID setpoint.
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive to show the VLTS [Thermostat Fault] when the input terminal is ON.
Note:
This function is active when the drive is running.
V/f
OLV/PM
OLV/PM EZOLV
Sets digital input 1 to use in DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV/PM
OLV/PM EZOLV
Sets digital input 2 to use in DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV/PM EZOLV
OLV/PM
Sets digital input 3 to use in DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV/PM
OLV/PM EZOLV
Sets digital input 4 to use in DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV/PM
OLV/PM EZOLV
Sets digital input 5 to use in DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV/PM EZOLV
OLV/PM
Sets digital input 6 to use in DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV/PM
OLV/PM EZOLV
Sets digital input 7 to use in DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
1.10 H: Terminal Functions
Description
Ref.
298
299
299
299
299
300
300
300
300
300
300
300
1
300
300
300
57