YASKAWA HV600 Manual page 285

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

A: Accel/Decel Ramp Hold
Setting Value
Function
A
Accel/Decel Ramp Hold
If the terminal is deactivated, the drive restarts acceleration and deceleration.
When the acceleration/deceleration ramp hold terminal is activated and d4-01 = 1 [Freq Reference Retention Select =
Enabled], the drive will store the output frequency in memory. While the acceleration/deceleration ramp hold
command is activated, the drive will always restart the motor at this output frequency.
Note:
Refer to
d4-01: Freq Reference Hold Selection on page 242
B: Overheat Alarm (oH2)
Setting Value
Function
B
Overheat Alarm (oH2)
C: Analog Terminal Enable Selection
Setting Value
Function
C
Analog Terminal Enable
Selection
ON : Terminal selected with H3-14 is enabled
OFF : Terminal selected with H3-14 is disabled
E: ASR Integral Reset
Setting Value
Function
E
ASR Integral Reset
ON : P control
OFF : PI control
F: Not Used
Setting Value
Function
F
Not Used
Through Mode uses the signal input to the terminal as a digital input for the upper sequence through a communication
option or MEMOBUS/Modbus communications. This input signal does not have an effect on drive operation.
10: Up Command
Setting Value
Function
10
Up Command
ON : Increases the frequency reference.
OFF : Holds the current frequency reference.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM
OLV/PM EZOLV
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output frequency that was
stored in the drive at the time of the pause, and restarts motor operation.
for more information.
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive to display an oH2 [Drive Overheat Warning] alarm when the input terminal is ON. The alarm does not have an effect
on drive operation.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command that enables or disables the terminals selected in H3-14 [Analog Input Terminal Enable Sel].
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
V/f
OLV/PM
OLV/PM EZOLV
Use this setting for unused terminals or to use terminals in through mode.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to use a push button switch to increase the drive frequency reference. You must also set Setting 11 [Down
Command].
2.8 H: Terminal Functions
Description
Description
Description
Description
Description
Description
2
285