1.10 H: Terminal Functions
No.
Name
(Hex.)
H3-10
Terminal A2 Function
Selection
(0418)
H3-11
Terminal A2 Gain Setting
(0419)
RUN
H3-12
Terminal A2 Bias Setting
(041A)
RUN
H3-13
Analog Input FilterTime
Constant
(041B)
H3-14
Analog Input Terminal
Enable Sel
(041C)
H3-16
Terminal A1 Offset
(02F0)
H3-17
Terminal A2 Offset
(02F1)
H3-40
Mbus Reg 15C1h Input
Function
(0B5C)
H3-41
Mbus Reg 15C2h Input
Function
(0B5F)
H3-42
Mbus Reg 15C3h Input
Function
(0B62)
H3-43
Mbus Reg Inputs
FilterTime Const
(117F)
H3-xx: MFAI Setting Values
Setting Value
Function
0
Frequency Reference
1
Frequency Gain
2
Auxiliary Frequency
Reference 1
3
Auxiliary Frequency
Reference 2
4
Output Voltage Bias
70
V/f
OLV/PM
OLV/PM EZOLV
Sets the function for MFAI terminal A2.
Note:
The default setting for H3-10 changes when b5-01 [PID Mode Setting] changes:
• b5-01 = 0 [Disabled]: 0
• b5-01 ≠ 0: B
V/f
OLV/PM EZOLV
OLV/PM
Sets the gain of the analog signal input to MFAI terminal A2.
V/f
OLV/PM
OLV/PM EZOLV
Sets the bias of the analog signal input to MFAI terminal A2.
V/f
OLV/PM
OLV/PM EZOLV
Sets the time constant for primary delay filters on MFAI terminals.
V/f
OLV/PM EZOLV
OLV/PM
Sets which terminal or terminals to enable when H1-xx = C [MFDI Function Selection =
Analog Terminal Enable Selection] is activated.
1 : Terminal A1 only
2 : Terminal A2 only
3 : Terminals A1 and A2
V/f
OLV/PM EZOLV
OLV/PM
Sets the offset level for analog signals input to terminal A1. Usually it is not necessary to
change this setting.
V/f
OLV/PM
OLV/PM EZOLV
Sets the offset level for analog signals input to terminal A2. Usually it is not necessary to
change this setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the MEMOBUS AI1 function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the MEMOBUS AI2 function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the MEMOBUS AI3 function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the time constant to apply a primary delay filter to the MEMOBUS analog input
register values.
V/f
OLV/PM EZOLV
OLV/PM
The input value from the MFAI terminal set with this function becomes the master frequency reference.
V/f
OLV/PM EZOLV
OLV/PM
The drive multiplies the analog frequency reference with the input value from the MFAI set with this function.
V/f
OLV/PM EZOLV
OLV/PM
Sets Reference 2 through multi-step speed reference to enable the command reference (Auxiliary Frequency Reference
1) from the analog input terminal set here. This value is a percentage where the Maximum Output Frequency setting is
a setting value of 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV/PM
OLV/PM EZOLV
Sets Reference 3 through multi-step speed reference to enable the command reference (Auxiliary Frequency Reference
2) from the analog input terminal set here. This value is a percentage where the Maximum Output Frequency setting is
a setting value of 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
V/f
OLV/PM EZOLV
OLV/PM
Set this parameter to input a bias signal and amplify the output voltage.
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
Ref.
(Range)
Determined by b5-01
327
(0 - 31)
100.0%
327
(-999.9 - +999.9%)
0.0%
328
(-999.9 - +999.9%)
0.03 s
328
(0.00 - 2.00 s)
2
328
(1 - 3)
0
328
(-500 - +500)
0
328
(-500 - +500)
F
329
(4 - 2E)
F
329
(4 - 2E)
F
329
(4 - 2E)
0.00 s
329
(0.00 - 2.00 s)
Ref.
329
330
330
330
330