2.6 E: Motor Parameters
Note:
The voltage values in the figures are for 208 V class drives. Multiply the values by 2 for 480 V class drives.
2011, 2017, 4005, 4008
B : High Trq, 60Hz, 65% Vmin boost
Use this pattern when high torque is necessary during start up.
Select this pattern only in these conditions:
• The wiring distance between the drive and motor is 150 m (492.1 ft) minimum.
• There is an AC reactor connected to the drive output.
Note:
The voltage values in the figures are for 208 V class drives. Multiply the values by 2 for 480 V class drives.
2011, 2017, 4005, 4008
C : High Freq, 60Hz base, 90Hz max
Use this constant output pattern to rotate motors at more than 60 Hz. Output voltage is constant when you operate at
more than 60 Hz.
Note:
The voltage values in the figures are for 208 V class drives. Multiply the values by 2 for 480 V class drives.
2011, 2017, 4005, 4008
D : Const Trq, 60 Hz base, 120 Hz max
Use this constant output pattern to rotate motors at more than 60 Hz. Output voltage is constant when you operate at
more than 60 Hz.
Note:
The voltage values in the figures are for 208 V class drives. Multiply the values by 2 for 480 V class drives.
250
2024 - 2169, 4011 - 4077
2024 - 2169, 4011 - 4077
2024 - 2169, 4011 - 4077
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
2211 - 2273, 4096 - 4302
2211 - 2273, 4096 - 4302
2211 - 2273, 4096 - 4302