YASKAWA HV600 Manual page 121

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
U4-09
LED Check
(005E)
U4-10
kWh, Lower 4 Digits
(005C)
U4-11
kWh, Upper 5 Digits
(005D)
U4-13
Peak Hold Current
(07CF)
U4-14
PeakHold Output Freq
(07D0)
U4-16
Motor oL1 Level
(07D8)
U4-18
Reference Source
(07DA)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM
OLV/PM EZOLV
Turns on the LED Status Ring and all of the keypad LEDs to make sure that the LEDs operate
correctly.
1.
Set o2-24 = 0 [LED Light Function Selection = Enable Status Ring & Keypad LED].
2.
Push
with U4-09 shown on the keypad.
All LEDs on the keypad and LED Status Ring will turn on.
Note:
When Safety input 2 CH is open (STo), READY will flash.
V/f
OLV/PM
OLV/PM EZOLV
Shows the lower 4 digits of the watt hour value for the drive.
Unit: 1 kWh
Note:
The watt hour is displayed in 9 digits. Monitor U4-11 [kWh, Upper 5 Digits] shows the upper 5
digits and U4-10 shows the lower 4 digits.
Example for 12345678.9 kWh:
U4-10: 678.9 kWh
U4-11: 12345 MWh
V/f
OLV/PM EZOLV
OLV/PM
Shows the upper 5 digits of the watt hour value for the drive.
Unit: 1 MWh
Note:
Monitor U4-11 shows the upper 5 digits and U4-10 [kWh, Lower 4 Digits] shows the lower 4
digits.
Example for 12345678.9 kWh:
U4-10: 678.9 kWh
U4-11: 12345 MWh
V/f
OLV/PM
OLV/PM EZOLV
Shows the hold value of the peak value (rms) for the drive output current.
Use U4-14 [PeakHold Output Freq] to show the drive output frequency at the time that the drive
holds the output current.
The drive will hold the peak hold current at the next start up and restart of the power supply.
The drive keeps the held value during baseblock (during stop).
The keypad shows the value of U4-13 in amperes (A). When you use serial communications to show
the monitor, the current is "8192 = drive rated current (A)." Use the formula: "Numerals being
displayed / 8192 × drive rated current (A)" to use the serial communication current value shown in
the monitor.
Unit: Determined by the drive model.
• 0.01 A: 2011 to 2046, 4005 to 4014
• 0.1 A: 2059 to 2273, 4021 to 4302
V/f
OLV/PM
OLV/PM EZOLV
Shows the output frequency at which the peak value (rms) of the drive output current is held.
The peak hold current can be monitored by U4-13 [Peak Hold Current].
The peak hold output frequency will be cleared at the next startup and restart of the power supply.
The drive keeps the value that was under hold during baseblock (during stop).
Unit: 0.01 Hz
V/f
OLV/PM EZOLV
OLV/PM
Shows the integrated value of oL1 [Motor Overload] as a percentage of oL1 detection level.
Unit: 0.1%
V/f
OLV/PM EZOLV
OLV/PM
Shows the selected frequency reference source.
The keypad shows the frequency reference source as "XY-nn" as specified by these rules:
X: Frequency reference
• 1: b1-01 [Frequency Reference Selection 1]
Y-nn: Frequency reference source
• 0-01: Keypad (d1-01 [Reference 1])
• 1-00: Analog input (unassigned)
• 1-01: MFAI terminal A1
• 1-02: MFAI terminal A2
• 2-02 to 2-17: Multi-step speed reference (d1-02 to d1-17 [Reference 2 to 8, Jog Reference])
• 3-01: Serial communications
• 4-01: Communication option card
• 7-01: DriveWorksEZ
• 9-01: Up/Down command
• B-00: Hand Reference 1 (Analog)
• B-01: Hand Reference 1 (S5-05 [HAND Frequency Reference])
Description
1.18 U: Monitors
MFAO Signal Level
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
10 V: 100%
No signal output available
1
121

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents