YASKAWA HV600 Manual page 195

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Note:
When the drive cannot accurately estimate the speed after you adjust this parameter, use Current Detection Speed Search.
b3-07: Speed Estimation Current Level 2
No.
Name
(Hex.)
b3-07
Speed Estimation Current
Level 2
(0197)
Expert
During Speed Estimation Speed Searches, when the speed estimation value aligns with the minimum output
frequency, increase the setting value in 0.1-unit increments. The limit of the output current during speed search is
automatically the drive rated current.
b3-08: Speed Estimation ACR P Gain
No.
Name
(Hex.)
b3-08
Speed Estimation ACR P
Gain
(0198)
b3-09: Speed Estimation ACR I Time
No.
Name
(Hex.)
b3-09
Speed Estimation ACR I
Time
(0199)
b3-10: Speed Estimation Detection Gain
No.
Name
(Hex.)
b3-10
Speed Estimation Detection
Gain
(019A)
Expert
If the drive detects ov [DC Bus Overvoltage] when you restart the motor, increase the setting value.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], the default setting is 1.00 and the setting range is 1.00 - 1.10.
b3-11: Spd Est Method Switch-over Level
No.
Name
(Hex.)
b3-11
Spd Est Method Switch-over
Level
(019B)
Expert
Note:
• 208 V class at 100% = 200 V
• 480 V class at 100% = 400 V
b3-12: Speed Search Current Deadband
No.
Name
(Hex.)
b3-12
Speed Search Current
Deadband
(019C)
Expert
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the level of current that flows to the motor during Speed Estimation Speed Search as a
coefficient of E2-03 [Motor No-Load Current] or E4-03 [Motor 2 Rated No-Load Current]. Usually
it is not necessary to change this setting.
V/f
OLV/PM
OLV/PM EZOLV
Sets the proportional gain for the automatic current regulator during Speed Estimation Speed Search.
Also adjusts speed search responsiveness. Usually it is not necessary to change this setting.
V/f
OLV/PM
OLV/PM EZOLV
Sets the integral time for the automatic current regulator during Speed Estimation Speed Search. Also
adjusts speed search responsiveness. Usually it is not necessary to change this setting.
V/f
OLV/PM
OLV/PM EZOLV
Sets the gain to correct estimated frequencies from Speed Estimation Speed Search.
V/f
OLV/PM EZOLV
OLV/PM
Uses the quantity of voltage in the motor to automatically switch the search method within the type
of speed measurement.
V/f
OLV/PM EZOLV
OLV/PM
Sets the minimum current detection level during Speed Search. If the drive does not do Speed
Estimation, increase this setting in 0.1-unit increments.
Description
Description
Description
Description
Description
Description
2.3 b: Application
Default
(Range)
1.0
(0.0 - 3.0)
Default
(Range)
Determined by A1-02 and
o2-04
(0.00 - 6.00)
Default
(Range)
Determined by A1-02 when
A1-02 ≠ 5
20.0 when A1-02 = 5
(0.0 - 1000.0 ms)
Default
(Range)
1.05
(1.00 - 1.20)
Default
(Range)
5.0%
(0.5 - 100.0%)
2
Default
(Range)
determined by o2-04
(2.0 - 10.0)
195

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents