YASKAWA HV600 Manual page 105

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
S3-10
PI2 Control Output
Lower Limit
(3223)
RUN
S3-11
PI2 Control Output Level
Sel
(3224)
S3-12
PI2 Control Disable
Mode Sel
(3225)
RUN
S3-13
PI2 Control Low
Feedback Lvl
(3226)
RUN
S3-14
PI2 Control Low
Feedback Time
(3227)
RUN
S3-15
PI2 Control High
Feedback Lvl
(3228)
RUN
S3-16
PI2 Control High
Feedback Time
(3229)
RUN
S3-17
PI2 Control Feedback Det
Sel
(322A)
RUN
S3-18
PI2 Control Custom Unit
1
(322B)
RUN
S3-19
PI2 Control Custom Unit
2
(322C)
RUN
S3-20
PI2 Control Custom Unit
3
(322D)
RUN
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the minimum output possible from the PI Auxiliary Control function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the PI2 controller output direction.
0 : Direct Acting (Normal Output)
1 : Inverse Acting (Reverse Output)
V/f
OLV/PM
OLV/PM EZOLV
Sets what U5-20 [PI2 Control Output] will output when disabled.
0 : No Output (0%)
1 : Lower Limit (S3-10)
2 : Setpoint
V/f
OLV/PM EZOLV
OLV/PM
Sets the secondary PI low feedback detection level.
Note:
Parameters S3-04 [PI2 Control Unit Selection], S3-03 [PI2 Control Decimal Place
Pos], and S3-02 [PI2 Control Transducer Scale] set the unit, resolution, and upper
limit.
V/f
OLV/PM
OLV/PM EZOLV
Sets the secondary PI low feedback detection delay time in seconds.
V/f
OLV/PM EZOLV
OLV/PM
Sets the secondary PI high feedback detection level.
Note:
Parameters S3-04 [PI2 Control Unit Selection], S3-03 [PI2 Control Decimal Place
Pos], and S3-02 [PI2 Control Transducer Scale] set the unit, resolution, and upper
limit.
V/f
OLV/PM EZOLV
OLV/PM
Sets the secondary PI high feedback detection delay time in seconds.
V/f
OLV/PM
OLV/PM EZOLV
Sets when the low and high feedback detection multifunction outputs (71h and 72h) for
PI2 Control are active.
0 : While PI2 Control Enabled
1 : Always
Note:
Feedback level detection compares PI2 Control Feedback from analog input H3-xx =
26 [MFAI Function Selection = PI2 Control Feedback] to these parameters:
• S3-13 [PI2 Control Low Feedback Lvl] for low feedback level detection
• S3-15 [PI2 Control High Feedback Lvl] for high feedback level detection
V/f
OLV/PM
OLV/PM EZOLV
Sets the first character of the PI2 Control custom unit display when S3-04 = 49 [PI2
Control Unit Selection = Custom(S3-18~20)].
V/f
OLV/PM EZOLV
OLV/PM
Sets the second character of the PI2 Control custom unit display when S3-04 = 49 [PI2
Control Unit Selection = Custom(S3-18~20)].
V/f
OLV/PM EZOLV
OLV/PM
Sets the third character of the PI2 Control custom unit display when S3-04 = 49 [PI2
Control Unit Selection = Custom(S3-18~20)].
1.16 S: Special Applications
Default
Ref.
(Range)
0.0%
443
(-100.0 - +100.0%)
0
443
(0, 1)
0
444
(0 - 2)
0.00
444
(0.00 - 600.00)
1.0 s
444
(0.0 - 25.5 s)
100.00
444
(0.00 - 600.00)
1.0 s
444
(0.0 - 25.5 s)
0
444
(0, 1)
41
445
(20 - 7A)
41
445
(20 - 7A)
41
445
(20 - 7A)
1
105

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents