YASKAWA HV600 Manual page 224

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.4 C: Tuning
C1-04: Deceleration Time 2
No.
Name
(Hex.)
C1-04
Deceleration Time 2
(0203)
RUN
C1-05: Acceleration Time 3
No.
Name
(Hex.)
C1-05
Acceleration Time 3
(0204)
RUN
C1-06: Deceleration Time 3
No.
Name
(Hex.)
C1-06
Deceleration Time 3
(0205)
RUN
C1-07: Acceleration Time 4
No.
Name
(Hex.)
C1-07
Acceleration Time 4
(0206)
RUN
C1-08: Deceleration Time 4
No.
Name
(Hex.)
C1-08
Deceleration Time 4
(0207)
RUN
C1-09: Fast Stop Time
No.
Name
(Hex.)
C1-09
Fast Stop Time
(0208)
RUN
Note:
When L2-29 = 0 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 1] and you do KEB Auto-Tuning, the drive will
automatically set C1-09. If you must not change the Fast Stop time, do not do KEB Auto-Tuning.
These conditions will start the Fast Stop function:
• When the drive received the Fast Stop command from the MFDI terminal
• When you set Fast Stop (Use C1-09) for a parameter to set a stopping method when the drive detected a fault
Set H1-xx = 15, 17 [MFDI Function Selection = Fast Stop (N.O.), Fast Stop (N.C.)].
When the drive receives the Fast Stop command, the motor ramps to stop in the deceleration time set in C1-09. After
the drive receives the Fast Stop command, you cannot start the drive operation again until deceleration is complete.
To clear the Fast Stop condition, deactivate the Fast Stop command, deactivate the Run command, then activate the
Run command again.
The terminal set for H2-xx = 4C [MFDO Function Selection = During Fast Stop] will activate during Fast Stop.
224
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time to decelerate from maximum output frequency to zero.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time to accelerate from zero to maximum output frequency.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time to decelerate from maximum output frequency to zero.
V/f
OLV/PM
OLV/PM EZOLV
Sets the length of time to accelerate from zero to maximum output frequency.
V/f
OLV/PM
OLV/PM EZOLV
Sets the length of time to decelerate from maximum output frequency to zero.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time that the drive will decelerate to zero for a Fast Stop.
Description
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
30.0 s
(0.1 - 6000.0 s)
Default
(Range)
30.0 s
(0.1 - 6000.0 s)
Default
(Range)
30.0 s
(0.1 - 6000.0 s)
Default
(Range)
30.0 s
(0.1 - 6000.0 s)
Default
(Range)
30.0 s
(0.1 - 6000.0 s)
Default
(Range)
10.0 s
(0.1 - 6000.0 s)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF