When the drive enters Sleep Mode, the software monitors the feedback to detect a flow-no flow condition. The drive
will deactivate the Sleep Mode operation and will go back to its normal operation when:
• The PID Error is more than this level in the time set in Y2-09 [Feedback Drop Detection Time]
• The output frequency is more than the level set in Y1-06 [Minimum Speed]
Note:
Set this parameter to 0.00 to disable the function.
Y2-09: Feedback Drop Detection Time
No.
Name
(Hex.)
Y2-09
Feedback Drop Detection
Time
(3C6C)
RUN
Y2-23: Anti-No-Flow Bandwidth
No.
Name
(Hex.)
Y2-23
Anti-No-Flow Bandwidth
(3C7A)
RUN
Note:
Do not set this parameter value too high, because operation can become unstable.
Y2-24: Anti-No-Flow Detection Time
No.
Name
(Hex.)
Y2-24
Anti-No-Flow Detection
Time
(3C7B)
RUN
Y2-25: Anti-No-Flow Release Level
No.
Name
(Hex.)
Y2-25
Anti-No-Flow Release Level
(3C7C)
RUN
Note:
The display unit and scaling change when the System Units change.

Y4: Application Advanced

Y4-01: Pre-Charge Level
No.
Name
(Hex.)
Y4-01
Pre-Charge Level
(3CFA)
RUN
Note:
The drive will stop when one of these conditions is true:
• The feedback level increases to more than Y4-01
• The pre-charge time set in Y4-03 [Pre-Charge Time] expires
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the time during which the software monitors the feedback to detect a flow/no-flow condition.
Refer to Y2-08 [Delta Feedback Drop Level] for more information.
V/f
OLV/PM
OLV/PM EZOLV
Sets the quantity of PI error bandwidth that the drive uses to detect an Anti- No-Flow condition.
V/f
OLV/PM
OLV/PM EZOLV
Sets the time delay before the drive starts the increased deceleration rate after it detects Anti-No-
Flow.
V/f
OLV/PM
OLV/PM EZOLV
Sets the amount below the setpoint which the feedback must decrease before the drive will disengage
Anti-No-Flow and return to normal PI operation.
V/f
OLV/PM EZOLV
OLV/PM
Sets the level at which the drive will activate the pre-charge function when the drive is running at the
frequency set in Y4-02 [Pre-Charge Frequency].
2.14 Y: Application Features
Description
Description
Description
Description
Description
Default
(Range)
10.0 s
(0.0 - 3600.0 s)
Default
(Range)
0.00%
(0.00 - 2.00%)
Default
(Range)
10.0 s
(1.0 - 60.0 s)
Default
(Range)
0.30%
(0.00 - 10.00%)
Default
(Range)
0.00%
(0.00 - 600.00%)