Setting Value
Function
C
Analog Terminal Enable
Selection
E
ASR Integral Reset
F
Not Used
10
Up Command
11
Down Command
12
Forward Jog
13
Reverse Jog
14
Fault Reset
15
Fast Stop (N.O.)
16
Motor 2 Selection
17
Fast Stop (N.C.)
18
Timer Function
19
PID Disable
1B
Programming Lockout
1E
Reference Sample Hold
20
External Fault (NO-
Always-Ramp)
21
External Fault (NC-
Always-Ramp)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the command that enables or disables the terminals selected in H3-14 [Analog Input Terminal Enable Sel].
ON : Input to the terminal selected with H3-14 is enabled
OFF : Input to the terminal selected with H3-14 is disabled
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
ON : P control
OFF : PI control
V/f
OLV/PM EZOLV
OLV/PM
Use this setting for unused terminals or to use terminals in through mode.
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to use a push button switch to increase the drive frequency reference. You must also set Setting 11
[Down Command].
ON : Increases the frequency reference.
OFF : Holds the current frequency reference.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to use a push button switch to decrease the drive frequency reference. You must also set Setting 10
[Up Command].
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to operate the motor in the forward direction at the Jog Frequency set in d1-17 [Jog Reference].
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to operate the motor in the reverse direction at the Jog Frequency set in d1-17 [Jog Reference].
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to reset the current fault when the Run command is inactive.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before
trying to reset a fault.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is
activated while the drive is operating.
V/f
OLV/PM
OLV/PM EZOLV
Sets the command for the drive to operate motor 1 or motor 2. Stop the motors before switching.
ON : Selects motor 2.
OFF : Selects motor 1.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is
activated while the drive is operating.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to start the timer function. Use this setting with Timer Output [H2-xx = 12].
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to disable PID control when b5-01 = 1 or 3 [PID Mode Setting = Standard or Fref + PID Trim].
ON : PID control disabled
OFF : PID control enabled
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to prevent parameter changes when the terminal is OFF.
ON : Programming Lockout
OFF : Parameter Write Prohibit
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to sample the frequency reference at terminals A1 or A2 and hold the frequency reference at that
frequency.
V/f
OLV/PM
OLV/PM EZOLV
When the terminal activates, the drive ramps to stop in the selected deceleration time. Fault relay output terminal MA-
MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is stopped or
running.
V/f
OLV/PM EZOLV
OLV/PM
When the terminal deactivates, the drive ramps to stop in the selected deceleration time. Fault relay output terminal
MA-MC will turn ON, and MB-MC will turn OFF. The drive always detects external faults whether the drive is
stopped or running.
1.10 H: Terminal Functions