2.4 C: Tuning
C4-02: Torque Compensation Delay Time
No.
Name
(Hex.)
C4-02
Torque Compensation Delay
Time
(0216)
RUN
Note:
If A1-02 = 8 [Control Method Selection = EZOLV], you cannot change the setting while the drive is running.
Set this parameter in these conditions:
• If there is vibration in the motor, increase the setting.
• If the motor speed or motor torque response is too slow, decrease the setting.
C4-07: Motor 2 Torque Compensation Gain
No.
Name
(Hex.)
C4-07
Motor 2 Torque
Compensation Gain
(0341)
RUN
In V/f Control, adjust the value in 0.05-unit increments for these conditions:
• When torque is not sufficient during low-speed operation of 10 Hz or less, increase the setting value
• When there is vibration in the motor or when the motor hunts when operating the drive with a light load, decrease
the setting value
• When you use a long motor cable, increase the setting.
Note:
Adjust C4-07 and make sure that the output current is not more than the drive rated current during low-speed operation.
C4-23: Current Control Gain
No.
Name
(Hex.)
C4-23
Current Control Gain
(1583)
RUN
Expert

C5: Auto Speed Regulator (ASR)

The ASR adjusts the torque reference to decrease the difference between frequency reference and motor speed. You
can use this function only when you set A1-02 = 8 [Control Method Selection = EZOLV].
Note:
The detected speed is the speed estimation value.
Before You Adjust ASR Parameters
• Do Auto-Tuning and set up all motor data correctly.
• Always connect the load to the motor when you make adjustments.
228
V/f
OLV/PM EZOLV
OLV/PM
Sets the torque compensation delay time. Usually it is not necessary to change this setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the gain for motor 2 torque compensation function when you use the Motor Switch function.
V/f
OLV/PM EZOLV
OLV/PM
Current control gain. Usually it is not necessary to change this parameter.
Figure 2.33 Speed Control Block Diagrams for EZOLV
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
Determined by A1-02
(0 - 60000 ms)
Default
(Range)
1.00
(0.00 - 2.50)
Default
(Range)
1.00
(0.50 - 2.50)