1.5 b: Application
No.
Name
(Hex.)
b5-41
PID Output 2 Unit
(0160)
b5-42
PID Output 2 Calc Mode
(0161)
RUN
b5-43
PID Out2 Monitor MAX
Upper4 Dig
(0162)
RUN
b5-44
PID Out2 Monitor MAX
Lower4 Dig
(0163)
RUN
b5-45
PID Out2 Monitor MIN
for Linear
(0164)
RUN
32
V/f
OLV/PM EZOLV
OLV/PM
Sets the display units in U5-14 [PID Out2 Upr4 Digits] and U5-15 [PID Out2 Lwr4
Digits].
0 : "WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 : °F: Fahrenheit
4 : ft
3
/min: cubic feet/min
5 : m
3
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 : "Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(b5-68~70)
50 : None
V/f
OLV/PM EZOLV
OLV/PM
Sets how to calculate the original PID output.
0 : Linear
1 : Square Root
2 : Quadratic
3 : Cubic
Note:
Used for U5-14 [PID Out2 Upr4 Digits] and U5-15 [PID Out2 Lwr4 Digits] only.
V/f
OLV/PM
OLV/PM EZOLV
Sets the upper 4 digits of the maximum monitor value. Used with b5-44 [PID Out2
Monitor MAX Lower4 Dig] to set maximum monitor value of U5-14 [PID Out2 Upr4
Digits] and U5-15 [PID Out2 Lwr4 Digits] at maximum frequency.
Note:
Used for U5-14 [PID Out2 Upr4 Digits] and U5-15 [PID Out2 Lwr4 Digits] only.
V/f
OLV/PM EZOLV
OLV/PM
Sets the lower 4 digits of the maximum monitor value. Used with b5-43 [PID Out2
Monitor MAX Upper4 Dig] to set maximum monitor value of U5-14 [PID Out2 Upr4
Digits] and U5-15 [PID Out2 Lwr4 Digits] at maximum frequency.
Note:
Used for U5-14 [PID Out2 Upr4 Digits] and U5-15 [PID Out2 Lwr4 Digits] only.
V/f
OLV/PM EZOLV
OLV/PM
Sets the minimum display value to show when at zero speed. Only effective when b5-42 =
0 [PID Output 2 Calc Mode = Linear].
Note:
Used for U5-14 [PID Out2 Upr4 Digits] and U5-15 [PID Out2 Lwr4 Digits] only.
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
Ref.
(Range)
0
211
(0 - 50)
0
212
(0 - 3)
0
212
(0 - 9999)
0.00
213
(0.00 - 99.99)
0.0
213
(0.0 - 999.9)