2.11 o: Keypad-Related Settings

o5: Log Function

The data log function saves drive status information as a CSV file in the microSD memory card in the keypad.
Monitors Ux-xx are the source of data log information. You can record a maximum of 10 monitors.
Change the HOA keypad screen from the main menu to the Diagnostic Tools screen and select the data log function.
Set the number of the monitor to record and the sampling time, then start to record the data log.
No.
o5-03
Log Monitor Data 1
o5-04
Log Monitor Data 2
o5-05
Log Monitor Data 3
o5-06
Log Monitor Data 4
o5-07
Log Monitor Data 5
o5-08
Log Monitor Data 6
o5-09
Log Monitor Data 7
o5-10
Log Monitor Data 8
o5-11
Log Monitor Data 9
o5-12
Log Monitor Data 10
Note:
• Do not de-energize the drive or disconnect the keypad from the drive during log transfer communication. A loss of connection can cause the
log function to fail after you restore power or connect the keypad
• You can use a microSDHC card that has a maximum of 32 GB capacity.
Log File Specifications
Item
File storage location
Filename
Maximum number of files
Character code
Line break code
Separating character
Header Rows
Log File Configuration
The [Log_Files] folder is created in the root directory of the micro SD card. This is where the log data is stored as
CSV files. Log data files are created in this configuration. The number of rows changes when the number of selected
monitors change.
First row
Drive information
Second row
Log data information
Third row
Log data 1
:
Log data 2
:
Log data 3
:
:
Last row
Log data n
424
Table 2.66 Setting Parameters for Data Log Items
Name
A folder called [Log_File] is created in the root directory of the micro SD card.
GLOG0xxx.csv
Note:
[xxx] identifies a 3-digit decimal number
999 (GLOG0001.csv to GLOG0999.csv)
ASCII code
<CR><LF>
[ , ] (Commas)
First Row: Drive information including Drive Model, software version, control method, and sampling time
Second Row: Log data information including the monitor number, number decimal points, and unit code
Default
101
U1-01 [Frequency Reference]
102
U1-02 [Output Frequency]
103
U1-03 [Output Current]
107
U1-07 [DC Bus Voltage]
108
U1-08 [Output Power]
000
Not selected
110
U1-10 [Input Terminal Status]
112
U1-12 [Drive Status]
000
Not selected
000
Not selected