L5: Fault Restart - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

L4-05: Fref Loss Detection Selection
No.
Name
(Hex.)
L4-05
Fref Loss Detection
Selection
(049D)
Enables the detection of a loss of an analog frequency reference when MFAI terminals (A1 and A2) input the
frequency reference. Set H2-01 to H2-03 = C [MFDO Function Selection = Frequency Reference Loss] to enable this
function.
If the frequency reference is less than 10% in 400 ms, the drive detects frequency reference loss.
0 : Stop
The drive follows the frequency reference and stops the motor.
1 : Run at (L4-06 x Last Reference)
The drive continues to operate at the frequency reference value set in L4-06 [FreqReference at Reference Loss]. When
you return the external frequency reference value, the drive continues to operate with the frequency reference.
L4-06: Frequency Reference @Loss of Ref
No.
Name
(Hex.)
L4-06
Frequency Reference @Loss
of Ref
(04C2)
Set L4-05 = 1 [FreqReference Loss Detect Select = Run@L4-06PrevRef] to enable this parameter.
L4-07: Speed Agree Detection Selection
No.
Name
(Hex.)
L4-07
Speed Agree Detection
Selection
(0470)
0 : No Detection during Baseblock
Detects the frequency while the drive is operating. When the drive turns off its output, it will not detect frequency.
1 : Detection Always Enabled

L5: Fault Restart

The Auto Restart function tries to keep machines operating when the drive detects a transient fault.
The drive can do a self-diagnostic check and continue the operation after a fault. If the cause of the fault goes away,
the drive does speed search and restarts. It will not stop and the drive will not record a fault history. Use L5-02 [Fault
Contact at Restart Select] to select the operation of fault relay signals during Auto Restart operation.
The Auto Restart function sets the drive to try to automatically restart the drive a set number of times in a set time. If
the number of Auto Restart tries is more than the set value during the set time, drive output shuts off and operation
stops. If this happens, remove the cause of the fault and manually restart the drive.
The drive can do Auto Restart when it detects these faults:
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the operation when the drive detects a loss of frequency reference.
Figure 2.93 Detection of Frequency Reference Loss
V/f
OLV/PM EZOLV
OLV/PM
Sets the frequency reference as a percentage to continue drive operation after it detects a frequency
reference loss. The value is a percentage of the frequency reference before the drive detected the loss.
V/f
OLV/PM EZOLV
OLV/PM
Sets the condition that activates speed detection.
Description
Description
Description
2.9 L: Protection Functions
Default
(Range)
1
(0, 1)
Default
(Range)
80.0%
(0.0 - 100.0%)
Default
(Range)
0
(0, 1)
2
369