S: Special Applications; S1: Dynamic Noise Control - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.12 S: Special Applications

2.12

S: Special Applications

S parameters set these functions:
• Dynamic Noise Control
• Sequence Run Timers
• PI2 Control
• HAND/OFF/AUTO Mode Operation
• Emergency Override Function

S1: Dynamic Noise Control

The Dynamic Audible Noise Control Function suppresses the output voltage to decrease audible noise.
This function is available when A1-02 = 0 [Control Method Selection = V/f] and can help you quickly restore output
voltage after an impact caused a sudden increase in the time constant. Dynamic Audible Noise Control is useful in
applications where load impact is common. You cannot use b8-01 = 1 [Energy Saving Control Selection = Enabled]
and S1-01 = 1 [Dynamic Noise Control = Enabled] at the same time.
Set Parameters for Dynamic Noise Control
1.
Set S1-01 = 1 [Dynamic Noise Control = Enabled] to enable Dynamic Noise Control.
Note:
• When S1-01 = 1, the tolerance to an impact load will decrease compared to V/f Control without Energy Saving.
• You must disable Dynamic Noise Control for applications without an impact load.
The current level increases from the added load and improves the drive responsiveness.
2.
Increase S1-02 [Voltage Reduction Rate] to make the flux stronger and increase the torque.
Note:
The Dynamic Noise Control function will decrease the load movement to a minimum level.
3.
Decrease S1-03 [Voltage Restoration Level] and S1-04 [Voltage Restoration Off Level] to recover the voltage
more quickly during the impact load conditions.
Note:
Under certain conditions, voltage stability may be unsatisfactory.
4.
Decrease S1-05 [Volt Restore Sensitivity Time K] to decrease the voltage level and increase the voltage
restoration speed when the load increase.
5.
Decrease S1-06 [Volt Restore Impact Load Time K] to increase drive response to an impact load.
When the output voltage is unstable, increase these values to decrease the load response:
• Difference between S1-03 and S1-04
• S1-05
• S1-06
S1-01: Dynamic Noise Control
No.
Name
(Hex.)
S1-01
Dynamic Noise Control
(3200)
0 : Disabled
1 : Enabled
430
V/f
OLV/PM EZOLV
OLV/PM
Sets the function that decreases the output voltage in variable torque applications to decrease audible
noise.
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
1
(0, 1)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents