T: Motor Tuning; T0: Tuning Mode Selection; T1: Induction Motor Auto-Tuning; T2: Pm Motor Auto-Tuning - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

1.17 T: Motor Tuning

1.17

T: Motor Tuning

T0: Tuning Mode Selection

No.
Name
(Hex.)
T0-00
Tuning Mode Selection
(1197)

T1: Induction Motor Auto-Tuning

No.
Name
(Hex.)
T1-00
Motor 1/Motor 2
Selection
(0700)
T1-01
Auto-Tuning Mode
Selection
(0701)
T1-02
Motor Rated Power
(0702)
T1-03
Motor Rated Voltage
(0703)
T1-04
Motor Rated Current
(0704)
T1-05
Motor Base Frequency
(0705)
T1-06
Number of Motor Poles
(0706)
T1-07
Motor Base Speed
(0707)
T1-11
Motor Iron Loss
(070B)

T2: PM Motor Auto-Tuning

No.
Name
(Hex.)
T2-01
PM Auto-Tuning
Selection
(0750)
T2-02
PM Motor Code Selection
(0751)
110
V/f
OLV/PM EZOLV
OLV/PM
Sets the type of Auto-Tuning.
0 : Motor Parameter Tuning
V/f
OLV/PM EZOLV
OLV/PM
Sets which motor to tune when motor 1/2 switching is enabled.
You can only use the keypad to set this parameter. You cannot use external input terminals
to set it.
Note:
This parameter is available when H1-xx = 16 [Motor 2 Selection]. The keypad will not
show this parameter when H1-xx ≠ 16.
1 : Motor 1 (sets E1-xx, E2-xx)
2 : Motor 2 (sets E3-xx, E4-xx)
V/f
OLV/PM
OLV/PM EZOLV
Sets the type of Auto-Tuning.
0 : Rotational Auto-Tuning
2 : Stationary Line-Line Resistance
V/f
OLV/PM
OLV/PM EZOLV
Uses the units set in o1-58 [Motor Power Unit Selection] to set the motor rated output
power.
V/f
OLV/PM EZOLV
OLV/PM
Sets the rated voltage (V) of the motor. Enter the base speed voltage for constant output
motors.
V/f
OLV/PM EZOLV
OLV/PM
Sets the rated current (A) of the motor.
V/f
OLV/PM EZOLV
OLV/PM
Sets the base frequency (Hz) of the motor.
V/f
OLV/PM
OLV/PM EZOLV
Sets the number of motor poles.
V/f
OLV/PM
OLV/PM EZOLV
Sets the motor base speed for Auto-Tuning (min
V/f
OLV/PM EZOLV
OLV/PM
Sets the iron loss for calculating the energy-saving coefficient.
V/f
OLV/PM EZOLV
OLV/PM
Sets the type of Auto-Tuning for PM motors.
0 : Manual Entry w/ Motor Data Sheet
1 : Stationary (Ld, Lq, R)
2 : Stationary (R Only)
4 : Rotational (Ld, Lq, R, back-EMF)
5 : High Frequency Injection
V/f
OLV/PM
OLV/PM EZOLV
Enter the PM motor code as specified by the rotation speed and motor output.
Description
Description
-1
(r/min)).
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
Ref.
(Range)
0
460
(0)
Default
Ref.
(Range)
1
460
(1, 2)
0
460
(0, 2)
Determined by o2-04
461
(0.00 - 650.00 HP)
Determined by o2-04
461
(208 V Class: 0.0 - 255.5
V,
480 V Class: 0.0 - 511.0
V)
Determined by o2-04
461
(10% to 200% of the
drive rated current)
60.0 Hz
461
(0.0 - 400.0 Hz)
4
461
(2 to 120)
-1
1750 min
(r/min)
461
(0 - 24000 min
-1
(r/min))
Determined by E2-11 or
462
E4-11
(0 - 65535 W)
Default
Ref.
(Range)
0
462
(0 - 5)
FFFF
462
(0000 - FFFF)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents