Test Run Checklist

Examine the items in this checklist and check each item before a test run.
Checked
No.
1
Correctly install and wire the drive as specified by this manual.
2
Energize the drive.
3
Set the voltage for the power supply in E1-01 [Input AC Supply Voltage].
Check the applicable items as specified by your control method.
WARNING! Sudden Movement Hazard. Correctly wire the start/stop and safety circuits before you energize the drive. If you
momentarily close a digital input terminal, it can start a drive that is programmed for 3-Wire control and cause serious injury or death
from moving equipment.
Checked
No.
Select the best V/f pattern for your application and motor characteristics.
4
Example: For a motor with a rated frequency of 60 Hz, set E1-03 = 1 [V/f Pattern Selection = Const Trq, 60Hz base, 60Hz max] as a standard V/f
pattern.
Checked
No.
Set E5-01 to E5-24 [PM Motor Settings].
5
Checked
No.
The keypad will show "Rdy" after starting to operate the motor.
6
To give the Run command and frequency reference from the keypad, push
Note:
7
When in HAND Mode,
8
If the motor rotates in the opposite direction during test run, switch two of the motor cables (U/T1, V/T2, W/T3).
Set E2-01 [Motor Rated Current (FLA)] and L1-01 [Motor Overload (oL1) Protection] correctly for motor thermal protection.
9
To supply the Run command and frequency reference from REMOTE source, make sure that the drive is in OFF Mode in HOME screen.
10
When terminal A1 is used for the frequency reference:
• Voltage input
– Set Jumper switch S1 on the drive to "V".
– Set H3-01 = 0 [Terminal A1 Signal Level Select = 0 to 10V (Lower Limit at 0)].
– Set H3-02 = 0 [Terminal A1 Function Selection = Frequency Reference].
11
• Current input
– Set Jumper switch S1 on the drive to "I".
– Set H3-01 = 2, 3 [Terminal A1 Signal Level Select = 4 to 20 mA, 0 to 20 mA].
– Set H3-02 = 0 [Terminal A1 Function Selection = Frequency Reference].
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Table 3.18 V/f Control [A1-02 = 0]
Table 3.19 PM Open Loop Vector Control [A1-02 = 5]
illuminates.
Description
Description
Description
Description
to set the drive to HAND Mode.

3.11 Test Run Checklist