YASKAWA HV600 Manual page 455

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Note:
• The drive will keep the S6-07 setting during a power-loss condition.
• Parameter o1-82 [Message Screen Display] sets how the drive will show the messages on the keypad. Refer to
Display on page 404
for more information.
S6-01: Emergency Override Speed
No.
Name
(Hex.)
S6-01
Emergency Override Speed
(3236)
Note:
• When A1-02 = 8 [Control Method Selection = EZOLV], E1-09 [Minimum Output Frequency] (E9-04 [Base Frequency]) sets the lower
limit, and E1-04 [Maximum Output Frequency] (E9-02 [Maximum Speed]) sets the upper limit.
• Parameter default is lower-limited to E1-09 (E9-04 when A1-02 = 8). The default setting will automatically increase when E1-09 (E9-04) >
S6-01.
S6-02: Emergency Override Ref Selection
No.
Name
(Hex.)
S6-02
Emergency Override Ref
Selection
(3237)
0 : Use S6-01 Reference
1 : Use Frequency Reference
2 : System PID Mode
3 : Independent PID Mode
S6-03: EMOVR Independent PID Scale
No.
Name
(Hex.)
S6-03
EMOVR Independent PID
Scale
(323A)
Note:
• S6-05 [EMOVR Independent PID Unit Digit] sets the resolution for this parameter.
• S6-04 [EMOVR Independent PID Unit] sets the units for this parameter.
S6-04: EMOVR Independent PID Unit
No.
Name
(Hex.)
S6-04
EMOVR Independent PID
Unit
(323B)
0 : "WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 : °F: Fahrenheit
3
4 : ft
/min: cubic feet/min
5 : m
3
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 : °C: Celsius
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the speed command for emergency override mode when S6-02 = 0 [Emergency Override Ref
Selection = Use S6-01 Reference].
V/f
OLV/PM EZOLV
OLV/PM
Sets the Emergency Override Speed Source:
V/f
OLV/PM EZOLV
OLV/PM
Sets the scaling on the Emergency PID Feedback and Setpoint (if programmed) Analog Inputs.
V/f
OLV/PM EZOLV
OLV/PM
2.12 S: Special Applications
Description
Description
Description
Description
Full Screen Information
Default
(Range)
1.50 Hz
(1.50 - 60.00 Hz)
Default
(Range)
0
(0 - 3)
Default
(Range)
100.00
(0.10 - 600.00)
Default
(Range)
48
(0 - 50)
455