YASKAWA HV600 Manual page 56

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

1.10 H: Terminal Functions
Setting Value
Function
52
Sequence Timer Cancel
60
DC Injection Braking
Command
61
Speed Search from Fmax
62
Speed Search from Fref
63
Field Weakening
65
KEB Ride-Thru 1
Activate (N.C.)
66
KEB Ride-Thru 1
Activate (N.O.)
67
Communications Test
Mode
68
High Slip Braking (HSB)
Activate
69
Jog Run 2
6A
Drive Enable
6D
AUTO Command
6E
HAND Command
70
Drive Enable 2
77
ASR Gain (C5-03) Select
7A
KEB Ride-Thru 2
Activate (N.C.)
56
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to cancel the currently active Sequence Timer.
ON : Cancel Active Sequence Timer
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to use DC Injection Braking to stop the motor.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available with a PM motor.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function to start speed search using an external reference although b3-01 = 0 [Speed Search Selection at Start
= Disabled].
Note:
The drive will detect oPE03 [Multi-Function Input Setting Err] if you set H1-xx = 61 and 62 at the same time.
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to use an external reference to start speed search although b3-01 = 0 [Speed Search Selection at Start
= Disabled].
Note:
The drive will detect oPE03 [Multi-Function Input Setting Err] if you set H1-xx = 61 and 62 at the same time.
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in d6-01
[Field Weakening Level] and d6-02 [Field Weakening Frequency Limit] when the input terminal is activated.
V/f
OLV/PM EZOLV
OLV/PM
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
V/f
OLV/PM
OLV/PM EZOLV
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
V/f
OLV/PM EZOLV
OLV/PM
Set the function for the drive to self-test RS-485 serial communications operation.
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to use high-slip braking to stop the motor.
V/f
OLV/PM EZOLV
OLV/PM
Causes the drive to ramp to the d1-17 [Jog Reference] frequency. The forward/reverse command from the 3-wire or 2-
wire 2 sequence sets the direction.
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to show dnE [Drive Enabled] on the keypad and ignore Run commands when the terminal is OFF.
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to operate the drive in AUTO Mode.
ON : AUTO Mode
OFF : OFF Mode or HAND Mode
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to operate the drive in HAND Mode.
ON : HAND Mode
OFF : OFF Mode or AUTO Mode
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to show dnE [Drive Enabled] on the keypad and ignore Run commands when the terminal is OFF.
ON : Run command is accepted.
OFF : Run command is disabled. When the drive is running, it stops according to b1-03 setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function to switch the ASR proportional gain set in C5-01 [ASR Proportional Gain 1] and C5-03 [ASR
Proportional Gain 2].
ON : C5-03
OFF : C5-01
V/f
OLV/PM EZOLV
OLV/PM
Sets operation of the KEB2 function through the KEB Ride-Thru 2 (N.C.).
ON : Normal operation
OFF : Deceleration during momentary power loss
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Ref.
295
295
295
296
296
296
296
296
297
297
297
297
297
298
298
298

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF