The drive automatically sets the parameters in
Table 2.8 Best Parameter Settings for Return Fan with PID Control Applications
No.
A1-02
b1-03
b1-04
b5-01
b5-03
b5-08
C1-01
H3-01
H3-02
H3-10
L5-01
o1-27
Y1-08
Y1-09
The drive saves the parameters in
Table 2.9 Parameters Saved as User Parameters with the Return Fan with PID Control Preset
User Parameter No.
A2-01
A2-02
A2-03
A2-04
A2-05
A2-06
A2-07
A2-08
A2-09
A2-10
A2-11
A2-12
A2-13
A2-14
A2-15
A2-16
A2-17
A2-18
A2-19
A2-20
A2-21
A2-22
A2-23
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Table 2.8
for a return fan with PID control application.
Name
Control Method Selection
Stopping Method Selection
Reverse Operation Selection
PID Mode Setting
Integral Time (I)
PID Primary Delay Time Constant
Acceleration Time 1
Terminal A1 Signal Level Select
Terminal A1 Function Selection
Terminal A2 Function Selection
Number of Auto-Restart Attempts
Custom Monitor 4
Low Feedback Level
Low Feedback Lvl Fault Dly Time
Table 2.9
as user parameters.
Parameter No. Saved
b1-03
b1-04
b2-09
b5-01
b5-03
b5-08
b5-09
C1-01
d2-03
H1-07
H3-01
H3-02
H3-10
L5-01
o1-24
o1-25
o1-26
Y1-04
Y1-05
Y1-08
Y1-09
Y2-01
Y2-02
2.2 A: Initialization Parameters
Optimal Value
0: V/f Control
1: Coast to Stop
1: Reverse Disabled
1: Standard
30.0 s
2.00 s
60.0 s
2: 4 to 20 mA
B: PID Feedback
16: Differential PID Feedback
10
505: PID DifferentialFdbk
2.00%
25 s
Name
Stopping Method Selection
Reverse Operation Selection
Pre-heat Current 2
PID Mode Setting
Integral Time (I)
PID Primary Delay Time Constant
PID Output Level Selection
Acceleration Time 1
Analog Frequency Ref Lower Limit
Terminal S7 Function Selection
Terminal A1 Signal Level Select
Terminal A1 Function Selection
Terminal A2 Function Selection
Number of Auto-Restart Attempts
Custom Monitor 1
Custom Monitor 2
Custom Monitor 3
Sleep Wake-up Level
Sleep Wake-up Level Delay Time
Low Feedback Level
Low Feedback Lvl Fault Dly Time
Sleep Level Type
Sleep Level
2
169