Note:
Refer to "d4-10: Up/Down Freq Lower Limit Select" for more information.
Figure 2.50
shows an example of how Up/Down command operates. In this example, the lower limit value of the
frequency reference is set in d2-02.
01] is enabled and disabled.
d4-01 = 0:
11: Down Command
Setting Value
Function
11
Down Command
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
Note:
• If you set only the Up command or only the Down command, the drive will detect oPE03 [Multi-Function Input Setting Err].
• If you set two or more of these functions at the same time, the drive will detect oPE03:
–Up/Down command
–Accel/Decel Ramp Hold
–Reference Sample Hold
–Offset Frequency 1, 2, 3 addition
• The Up/Down command does not function in these conditions:
–b1-01 = 2, 3 [Frequency Reference Selection 1 = Serial Communications, Option PCB]
–b1-02 ≠ 1 [Run Command Selection 1 ≠ Digital Input]
–Drive is in HAND mode
When you enter the Up command, the frequency reference increases. When you enter the Down command, the
frequency reference decreases.
The Up and Down commands have priority over all other frequency references. When you enable the Up/Down
command, the drive will ignore these frequency references:
• Frequency reference from Keypad [b1-01 = 0]
• Frequency reference from Analog Input [b1-01 = 1]
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
shows the time chart when Frequency Reference Hold Function [d4-
Figure 2.50
Figure 2.50 Up/Down Command Time Chart
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to use a push button switch to decrease the drive frequency reference. You must also set Setting 10 [Up
Command].
d4-01 = 1:
Description
2.8 H: Terminal Functions
287
2