Auto-Tuning automatically sets this parameter to the value input for [Motor Rated Power].

E5: PM Motor Settings

E5 parameters set PM motor data.
Set E5-01 to the motor code when you use a PM motor recommended by Yaskawa and the drive will automatically set
E5 and other related motor parameters to the optimal values.
Do Auto-Tuning for all other PM motors. If information from motor nameplates or test reports is available, you can
enter the E5 parameters manually.
Note:
• The keypad shows E5-xx only when A1-02 = 5 [Control Method Selection = OLV/PM].
• If you use A1-03 [Initialize Parameters] to initialize the drive, it will not reset E5-xx parameters.
E5-01: PM Motor Code Selection
No.
Name
(Hex.)
E5-01
PM Motor Code Selection
(0329)
Note:
If the drive hunts or shows an alarm after you enter a motor code, use the keypad to enter the value shown on the nameplate to E5-xx.
E5-02: PM Motor Rated Power
No.
Name
(Hex.)
E5-02
PM Motor Rated Power
(032A)
The drive will automatically set this parameter the next time you do Auto-Tuning.
• PM Motor Parameter Settings
• PM Stationary Auto-Tuning
• PM Rotational Auto-Tuning
E5-03: PM Motor Rated Current (FLA)
No.
Name
(Hex.)
E5-03
PM Motor Rated Current
(FLA)
(032B)
Note:
When the drive model changes, the display units for this parameter also change.
• 0.01 A: 2011 to 2046, 4005 to 4014
• 0.1 A: 2059 to 2273, 4021 to 4302
The drive automatically sets E5-03 to the value input for "PM Motor Rated Current" after you do these types of Auto-
Tuning:
• PM Motor Parameter Settings
• PM Stationary Auto-Tuning
• PM StaTun for Stator Resistance
• PM Rotational Auto-Tuning
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the motor code for Yaskawa PM motors. The drive uses the motor code to automatically set
some parameters to their correct settings.
V/f
OLV/PM EZOLV
OLV/PM
Sets the PM motor rated output in the units set in o1-58 [Motor Power Unit Selection].
V/f
OLV/PM EZOLV
OLV/PM
Sets the PM motor rated current (FLA).
Description
Description
Description
2.6 E: Motor Parameters
Default
(Range)
FFFF
(0000 - FFFF)
Default
(Range)
Determined by o2-04
(0.13 - 650.00 HP)
Default
(Range)
Determined by o2-04
(10% to 200% of the drive
rated current)
259